DKG-317 User Manual                                                                         V-01.19 

(01.10.2009)

 

 

 

 

 

 

- 22 -   

 

 
When  the  RUN  button  is pressed,  the  engine  starts  to  run  but  the  unit  gives  START  FAIL  alarm 
and then the engine stops:  

 
-The generator phase voltages are not connected to the unit. Measure the AC voltage between terminals 

U-V-W

 and 

Generator Neutral

 at the rear of the unit while the engine is running. A fuse protecting the 

generator phases may be failed. A misconnection may be occurred. If everything is OK, turn all the fuses 
off, and then turn all the fuses on, starting from the DC supply fuse. Then test the unit again. 
 
 

The unit is late to remove engine cranking: 

 
-The  generator  voltage  rises  lately.  Also  the  generator  remnant  voltage  is  below  20  volts.  The  unit 
removes starting with the generator frequency, and needs at least 20 volts to measure the frequency. If 
this situation is to be avoided, the only solution is to add an auxiliary relay. The coil of the relay will be 
between BATTERY (-) and charging alternator D+ terminal. The normally closed contact of the relay will 
be connected serially to the unit's START output. So the starting will also be removed when the D+ pulls 
to battery positive. 
 
 

The unit is inoperative: 

 
Measure  the  DC-supply  voltage  between  terminals  11  and  12  at  the  rear  of  the  unit.  If  OK,  turn  all  the 
fuses off, then turn all the fuses on, starting from the DC supply fuse. Then test the unit again. 
 
 

Programming mode can not be entered:  

 
The program lock input disables programming mode entry. Disconnect the program lock input from 
battery negative before modification. Do not forget to make this connection again to prevent unauthorized 
program modifications. 
 

 
 
 

12. DECLARATION OF CONFORMITY 

 
 

The unit conforms to the EU directives 

 

-73/23/EEC and 93/68/EEC (low voltage) 

 

-89/336/EEC, 92/31/EEC and 93/68/EEC (electro-magnetic compatibility) 

 

Norms of reference: 

 

 

EN 61010    (safety requirements) 

 

 

EN 50081-2 (EMC requirements) 

 

 

EN 50082-2 (EMC requirements) 

 
 

The CE mark indicates that this product complies with the European requirements for safety, 

health environmental and customer protection. 
 

Содержание DKG-317

Страница 1: ...wer measurement Genset power factor measurement Periodic maintenance request indicator Engine hours counter Event logging Statistical counters Field adjustable parameters RS 232 serial port Free MS Wi...

Страница 2: ...s 3 2 Digital Display 4 ALARMS AND WARNINGS 5 MODES OF OPERATION 6 OTHER FEATURES 6 1 Remote start operation 6 2 Sender type selection 6 3 Service Request Display 6 4 Engine Hour Meter 6 5 Modem conne...

Страница 3: ...the retaining steel spring and connectors from the unit then pass the unit through the mounting opening The unit will be maintained in its position by the steel spring Engine body must be grounded fo...

Страница 4: ...porate appropriate short circuit backup protection e g a fuse or circuit breaker of High Breaking Capacity HBC at least 1500A 6 Use cables of adequate current carrying capacity at least 0 75mm 2 and t...

Страница 5: ...table from a list 19 START RELAY Output 10A 28VDC This relay controls the engine cranking 20 FUEL RELAY Output 10A 28VDC This relay is used for fuel solenoid control It is internally connected to term...

Страница 6: ...hours or time duration after previous service has elapsed ALARM GROUP Red If a fault condition resulting to the engine shutdown has occurred the related alarm led turns on steadily If a warning condi...

Страница 7: ...generator phase to neutral voltages UV VW WU generator phase to phase voltages If the service counters group is displayed then this display will show the counter name In programming mode it displays P...

Страница 8: ...med HIGH TEMPERATURE Set if a signal is detected at the High Temperature Switch input or the coolant temperature value measured from the sender is above the programmed limit Warning P_017 and alarm P_...

Страница 9: ...ter P_042 is set to 1 then the unit will enter to the Remote Start operation In this mode the engine will run and stop with the Remote Start signal It is also necessary to set the program parameter P_...

Страница 10: ...ing engine hours and the remaining time limit are kept stored in a non volatile memory and are not modified by power supply failures The remaining time and engine hours to service may be checked via t...

Страница 11: ...0 CASECOM USB TO SERIAL CONVERTER MODEL RS 01 7 EVENT LOGGING The unit keeps records of the last 12 events in order to supply information for the service personal The events are stored in a circular m...

Страница 12: ...er failures To exit the program mode press one of the mode selection keys If no button is pressed during 1 minute the program mode will be cancelled automatically Pgm Definition Unit Std Val Descripti...

Страница 13: ...High Battery Voltage Alarm V 33 0 If the battery voltage goes over this limit this will generate a BATTERY alarm and the engine will stop 15 Low Oil Pressure Warning Bar 1 5 If the oil pressure measu...

Страница 14: ...limits P_008 P_011 and SPEED FAULT alarm occurs 25 Not used 26 Preheat timer sec 1 This is the time after the fuel solenoid is energized and before the genset is started During this period the PREHEA...

Страница 15: ...ngine Hours hours 200 The SERVICE REQUEST led indicator will turn on after this quantity of engine hours from the last service If the period is set to 0 no SERVICE REQUEST will be generated depending...

Страница 16: ...n 22 74 RELAY 10 function 23 75 RELAY 11 function 24 76 RELAY 12 function 25 77 RELAY 13 function 26 78 RELAY 14 function 27 79 RELAY 15 function 28 80 RELAY 16 function 29 81 RELAY 17 function 30 82...

Страница 17: ...e 1 Battery positive 88 Response delay 0 0 No delay 1 Delayed 4sec HIGH TEMPERATURE SWITCH INPUT Pgm Description Std 89 Operation 0 0 Alarm the engine stops and horn relay operates 2 Warning the horn...

Страница 18: ...relay operates 2 Warning the horn relay operates 3 No operation 108 Fault monitoring 0 0 Always 1 After holdoff timer 2 When mains present 109 Latching 0 0 Non latching 1 Latching 110 Contact type 0 0...

Страница 19: ...t type 0 0 Normally open 1 Normally closed 129 Switching 0 0 Battery negative 1 Battery positive 130 Response delay 0 0 No delay 1 Delayed 4sec Parameters from P_131 to P_142 define the ohm bar charac...

Страница 20: ...red as 0 An example table is given below The sensor characteristics used in this table are 38 C 342 ohms 82 C 71 ohms 104 C 40 ohms 121 C 30 ohms Pgm Description Unit Value 143 Point_1 resistor ohm 30...

Страница 21: ...the Amp readings are correct Current transformers are not connected to the correct inputs or some of the CTs are connected with reverse polarity Determine the correct connections of each individual C...

Страница 22: ...between BATTERY and charging alternator D terminal The normally closed contact of the relay will be connected serially to the unit s START output So the starting will also be removed when the D pulls...

Страница 23: ...Internally connected to battery positive via 4700 ohm resistor Analog inputs Resistor input 0 to 5000 ohms connected to the battery negative Sources 10 mA when closed to battery negative Measurement...

Страница 24: ...DKG 317 User Manual V 01 19 01 10 2009 24 14 CONNECTION DIAGRAM...

Отзывы: