DKG-255 User Manual Firmware V-1.0
- 22 -
P_09
STARTING RPM FUEL
parameter adjusts the fuel amount during engine cranking.
A high starting fuel adjustment helps the engine to fire faster.
However the minimum necessary amount of starting fuel should be used in order to minimize engine exhaust
smoke during cranking.
The Speed Ramp adjusts the time that the engine requires to reach the nominal speed from idle speed.
The engine will ramp faster to the nominal speed with increased values of
P_11
.
If the engine rpm goes over
P_03 Delayed Overspeed Limit
during
P_05 Overspeed Delay Timer
, this
will generate overspeed alarm. Overspeed alarm is set immediately if the engine rpm is above
P_04
Immediate Overspeed Limit
.
When an overspeed alarm occurs,
OVERSPEED
and
ERROR
leds will turn on and
“
err6
” message is
displayed on the screen.
Hold pressed
and
buttons together to reset overspeed alarm.
P_25 Save Configuration
parameter allows user to save the current configuration of the device.
The device offers 14 different memory locations to save the configuration. Thus different configurations can
be saved to different memory locations and any of them can be restored later.
The memory location 1 is reserved for the factory set configuration. It cannot be overwritten, but may be
restored anytime.
If the user selects the memory location number from
P_26 Restore Configuration
parameter, parameters
will be automatically configured accordingly.
In order to return to factory settings, P_26 must be set to1.
Firmware update can be done if the manufacturer releases an update about the operation of device.
The firmware file cannot be read from the unit and it is always required to get the original firmware file
from the manufacturer.
To force the device to firmware update mode,
P_28 Boot Mode
parameter must be set to 1.
The unit in BOOT LOADER mode will wait for a PC connection through its USB port. When the unit
establishes USB connection, the device will be automatically recognized by the PC and will appear as a
Device with Removable Storage. After deleting firmware file, copy the new firmware provided by Datakom
into this disk.
9.9. Firmware Update
9.8. Saving and Restoring the Configuration
9.7. Overspeed Alarm Adjustment
9.6. Speed Ramping Adjustment
9.5. Starting RPM Fuel Adjustment