micro inverter and then to the junction box. After laying out the grounding 

conductor, secure the top of the grounding clips back onto the micro inverters. 

 

 

WARNING 

Correct AC grounding and short circuit protection must be provided to ensure 

operational safety. 

 

Step 6: Connect the Micro Inverters 

6.1.

 

Remove the temporary shipping cap from the t-branch on the AC trunk cable 

and connect the micro inverter. Ensure the connection is secure and locked 

into place  by listening to “click”  sounds when both lock pins are fully 

inserted. 

 

        

   

 

 

WARNING

 

Correct AC grounding and short circuit protection must be provided to ensure 

operational safety. 

 

6.2.

 

Repeat for all micro inverters in the AC circuit. 

6.3.

 

For any unused connectors on the AC trunk cable, replace the temporary   

shipping cap with a Sealing Cap. Listen for a click as the Sealing Cap is 

connected to ensure that it is securely locked into place. 

 

Note : Please check which type of the trunk cable you have before ordering micro 

inverters. 

 

Step 7: Terminate the Unused End of the AC Trunk Cable 

7.1.

 

Strip 10mm (about 0.5in) of the outer sheath from the end of the AC trunk 

cable. 

7.2.

 

Each end cap has four parts: the sealing nut, clamp ring, seal and cap. Slide 

the sealing nut, clamp ring and then the seal onto the AC trunk cable. 

7.3.

 

Insert the individual wires into the slots inside the cap of the end cap. 

7.4.

 

Screw the hex nut onto the cap. Use a wrench to ensure the hex nut is 

screwed in all the way to the base of the cap.   

 

 

 

WARNING

 

 

Ensure the AC trunk cable and end cap do not touch the roof by using cable 

clips or tie wraps to attach the trunk cable to the PV racking. Ensure that all 

cabling is located underneath the PV module. 

 

Step 8: Connect the AC Junction Box 

Connect the AC trunk cable to the AC junction box using the appropriate gland or 

strain relief fitting. The AC trunk cable requires a strain relief connector with an 

opening of 1.6 cm (0.6 in) in diameter. 

The wires in the AC trunk cable are identified by color: L1 is sheathed in Black, L2 

is sheathed in Red, Neutral is sheathed in White and Ground is sheathed in 

Green. Note the Neutral/White wire is unused. 

 

 

WARNING 

Although the AC trunk cable includes a grounding wire, the continuous grounding 

conductor or grounding washers is still required. 

 

Step 9: Connect the PV Modules 

Mount the PV modules above the micro inverters, and then connect each micro 

inverter to a PV module. (The micro inverter and PV module’s DC cables have two 

connectors. Connect the micro inverter positive connector to the PV module 

negative connector, and vice versa.) 

 

 

CAUTION 

Micro inverters and PV modules are installed using a one to two ratio. 

 

Содержание G640

Страница 1: ...G640 MI CRO I NVERTER U S E R M A N U A L...

Страница 2: ...OTECTION 7 INSTALLING THE MICRO INVERTER 8 INSTALLING ONTO A PV RACKING SYSTEM 8 POST INSTALLATION 10 COMMISSIONING AND OPERATING 10 GFDI FAULT 10 DISCONNECTING A MICRO INVERTER 10 MONITORING SYSTEM 1...

Страница 3: ...operation To reduce risk of burns use caution when working with micro inverters Do not disconnect the DC power source from the micro inverter without first disconnecting the AC power source Both AC an...

Страница 4: ...ogue pdf Citel MSB10 400 http www citel fr userfiles medias Datasheet fiche_anglaise MSB10 UL__A _F141103A pdf FCC Compliance This equipment has been tested and found to comply with the limits for a C...

Страница 5: ...e is recommended such as Belden 3105A however any twisted pair cable can be used such as CAT5 with some degradation of signal and distance Parts and Tools This section provides a list of equipment and...

Страница 6: ...o each G640 by completely isolating the internal DC circuit from the AC circuit and ground DC ground faults are detected on either the positive and or negative conductors of the DC circuit by a Ground...

Страница 7: ...ial number sticker on the DC side can be peeled off the micro inverter and adhered to the installation map template where the actual position on the roof would correspond to the same panel on the layo...

Страница 8: ...tion Align the connector to the position where the micro inverter will be installed Then secure the cable on either side of the rack using cable clips or tie wraps Note the G640 is the micro inverter...

Страница 9: ...as four parts the sealing nut clamp ring seal and cap Slide the sealing nut clamp ring and then the seal onto the AC trunk cable 7 3 Insert the individual wires into the slots inside the cap of the en...

Страница 10: ...allic enclosures metallic raceways metallic equipment or earth When a Ground fault occurs the GFDI will trigger the LED light to show continuous Red and the micro inverter will automatically disconnec...

Страница 11: ...the termination resistor switch on both the Data Logger and PLC Box should be switched ON If the distance between the Data Logger and PLC Box is less than 50m then the termination resistor switch on b...

Страница 12: ...connect the PV circuit from any grid power before installing the PLC box to the AC trunk cable or AC junction box Step 1 Connect the Data Logger to the Router There are two ways to connect the data lo...

Страница 13: ...he micro inverter Note To mount the data logger use the included wall mount frame Step 4 Connect the Data Logger to the PLC Box Insert the red black wiring into the RS485 connectors and then insert th...

Страница 14: ...Step1 Verify that any upstream AC disconnects as well as the dedicated circuit breakers for each AC circuit are functioning properly and are closed Step2 Verify that the AC voltages at the electrical...

Страница 15: ...rrectly use the steps below to troubleshoot the problem If the issue cannot be resolved using these steps please contact inverter maker s technical services Power LED did not turn on Verify that the P...

Страница 16: ...or local regulation PLC Box COMMUNICATION Serial Port Interface 1 x RS485 For Data Logger 1 Maximum Number of Devices Up to 24 Micro Inverters Maximum Transmission Distance2 Up to 164ft 50m MEMORY Int...

Страница 17: ...G 6 4 0 M i c r o I n v e r t e r U s e r M a n u a l G 6 4 0 U M d r a f t v1 20180928 2 0 1 8 D a r f o n E l e c t r o n i c s C o r p p 1 7 1 9 SAMPLE WIRING 240V 1...

Страница 18: ...C o r p p 1 8 1 9 INSTALLATION MAP TEMPLATE Use this map to draw the array and keep track of the micro inverters placement by serial number Peel off and use secondary serial number label on the micro...

Страница 19: ...d by Darfon Electronics Corp 167 Shan ying Road Gueishan Taoyuan 333 Taiwan R O C Tel 886 3 2508800 USA Office Darfon America Corp 103A Pioneer Way Mountain View CA 94041 Tel 1 650 316 6300 For more i...

Отзывы: