1. GENERAL
3
1.1 Introduction
The DanX 1/2/3 type HP and XD equipment is designed for the use for ventilation, humidity
and temperature control in private and hotel swimming pool areas. The use of the unit
includes the required inspection and maintenance for these units, which is described in the
final chapter of this manual.
Unloading, transportation, assembly and connecting of the DanX 1/2/3 should only be
carried out by trained professionals
or by people supervised by authorized staff. It is the
responsibility of the fitter to read and understand this guide and other given information.
1.2 Foundation for the unit
The DanX 1/2/3 unit must be installed in a location that meets the following requirements:
•
The supporting structure must be level, stable and vibration-free.
•
The supporting structure must be able to bear the weight of the unit (up to 500 kg).
•
The deflection of the substructure should be max. 1 mm/m.
•
For the connection of the condensate drain, it is necessary that the height between
condense outlet of the unit and the substructure is at least the required height for the
water trap.
1.3 Minimum distances
For the operation, maintenance and servicing of parts as heating coils, dampers, filters and
others a minimum clearance of 850/850/1100 mm (DanX 1/2/3) between inspection side of
the unit and the wall should be foreseen. It is also recommended to have a minimum
clearance of 200 mm between the wall and the side of the unit were the water outlet is
located.