4. CONTROLS
24
With a PIR sensor:
Enter the time program and change the standard two points (Open Pool and Closed Pool
time) to only Closed Pool with the start time 00:00 (afterwards it will be shown as 12:00 AM
in the display) and delete the Open Pool time completely from the program. Be aware that
you have to do that for every day. Under Closed Pool you can then set the wanted fan speed
for closed mode (high, low or stop).
With a pool cover switch:
Enter the time program and change the standard two points (Open Pool and Closed Pool
time) to only Open Pool with the start time 00:00 (afterwards it will be shown as 12:00 AM in
the display) and delete the Closed Pool time completely from the program. Be aware that
you have to do that for every day. Under Open Pool you can then set the wanted fan speed
for open mode (high, or low).
See also chapter 4.7.1 how you make the changes in the Unit Time Program.
4.4.5.5 WCC pump exercise
Under the point WCC Pump exercise you can configure how often the pump for the water
cooled condenser should run for a few minutes to get the still standing water exchanged in
the condenser. You have the possibility to set it once an hour, day or week.
4.4.5.6 Closed Mode Cooling
Under the point Closed Mode Cooling you can configure if your unit should cool (free and
active cooling) when the pool is closed or not. Normally this point is set to NO, but for
example in therapy pools, or hot countries it will be set to YES.