4. CONTROLS
23
4.4.5.1 Filter check date
Under Filter Check Date the date for the annual filter check can be given in. The first or two
figures indicate the month, the next two figures indicate the day, when the filter check should
appear on the display. 912 for example stand for September the 12
th
.
4.4.5.2 Heating coil
Under the point Heating Coil you can configure if your unit is equipped either with water or
electrical heating coil.
4.4.5.3 Wake up function
If using the Wake Up function it is essential that the standard humidity and temperature duct
sensor is being placed directly after the return air duct grill to be able to measure the
humidity and temperature in the room without any air movement (fans stopped). If this is not
possible, the duct sensor has to be placed directly in the room or replaced by a room
humidistat / temperature sensor.
With the wake up function you can choose if the unit should start up automatically at too high
humidity or too low temperature, if you have set the unit to be stopped in the time program. If
you have chosen YES, the unit will run as long as it takes to reach the wanted set point.
When the set point is reached the unit will then automatically stop again. If you choose NO
the unit will not start up, even if the room conditions not correspond to the wanted set points.
4.4.5.4 External Signal (PIR sensor or pool cover switch)
If you want to start or stop the unit with the help of an external contact you can define this
under External Signal configuration. Here you can choose between the following possibilities
when the external signal is activated:
•
PIR Open Low (When there is a signal from the PIR sensor the unit will go in Open Pool
mode with the fans in low speed)
•
PIR Open High (When there is a signal from the PIR sensor the unit will go in Open Pool
mode with the fans in high speed)
•
Cover Closed Low (When there is a signal from the pool cover switch the unit will go in
Closed Pool mode with the fans in low speed)
•
Cover Closed High (When there is a signal from the pool cover switch the unit will go in
Closed Pool mode with the fans in high speed)
•
Cover Closed Stop (When there is a signal from the pool cover switch the unit will go in
Closed Pool mode with the fans stopped)