4. CONTROLS
36
4.10.2 Remote access
The MVC WEB is operated via a standard web browser. By default, an integrated web server
provides all operation pages for a full browser-based operation. Through the consequent use
of software standards, any PC platform can be used as an operator interface (client). Other
than the operating system and Internet Explorer, Chrome or Firefox, no software needs to be
installed on the client PCs.
To access the MVC WEB controller through a LAN network you have to allocate a valid and
permanent IP address to the controller, which is reachable within the LAN.
4.10.3 LAN password
To enter the controller through a browser you need a password as if you would enter through
the display (see chapter 4.4.1.1).
There are three different access levels in the program, depending on the username and
password. To change the Time Program or set point, you have to use the level 1 password
for the operator to get access. With level 2, all points can be set into manual to test the unit.
On access level 3 you can change passwords, users and the IP address. Furthermore you
can set up alarm e-mails.
* Please ask Dantherm
4.10.4 Change of LAN IP address
The LAN IP address of the MVC WEB controller is from the factory set up with the following
address:
IP:
192.168.1.202
Subnet Mask:
255.255.255.0
Gateway:
192.168.1.1
This address will maybe work in some smaller home networks, but if you have a larger
network you surly have to change the LAN IP address. This you do in the following way:
•
Make a local connection to the MVC WEB controller (see chapter 4.10.1)
•
Open a browser on your computer. Enter the IP address for the USB connection which
is always 192.168.255.241 and enter the password for the System Administrator
which you can get from your Dantherm dealer (see chapter 4.10.3)
•
After Login you will see the flow diagram of the unit (see chapter 4.10.5)
User Name
Access level
Password
Possibilities
Operator
1
operator
Time Program, set point changes
BuildingEngineer
2
honeywell
Points can be set to manual
SystemAdmin
3
*
IP address and password change.
E-mail set up