RS-485 Interface
RS-485 Interface implements Modbus RTU protocol as slave device. Device doesn't have address .
Settings: 115200, N, 8, 1. and accepts requests to any address.
Code Functions
0x06
preset single register
0x10
preset multiple registers
0x03
read holding registers
Register Byte
Database
parameter
Min
Max
De-
fault
Description
2
2
Comp_
state
0
1
0
Compressor state:
0 - Compressor stopped 1 - Compressor works
3
Fan_state
0
1
0
FAN state:
0 - FAN stopped 1 - FAN works
3
4
Sole_state
0
1
0
Solenoid valve:
0
- closed
1
- open
5
ExFan_state
0
1
0
Exhaust FAN state:
0 - FAN stopped
1 - FAN works
4
6
Heat1_state
0
1
0
Heater 1 state:
0 - Heater turned off
1 - Heater turned on
7
Heat2_state
0
1
0
Heater 2 state:
0 - Heater turned off
1 - Heater turned on
5
8
Alarm1_
state
0
1
0
Alarm 1 output:
0 - Alarm out turned off
1 - Alarm out turned on
9
Alarm2_
state
0
1
0
Alarm 2 output:
0 - Alarm out turned off
1 - Alarm out turned on
6
10
Evap_
temp1
(decimal)
-40
100
0
Temperature from evaporator 1:
decimal: may be used as integer value of
temperature
fraction: may be recalculated to value after
decimal point.
To get whole value use the equation in float point
values "val = d (fraction / 256)"
11
Evap_
temp1
(fraction)
-40
100
0
Содержание CDP 50
Страница 9: ...9...
Страница 14: ...14 EN CDP 40 50 70 CDP 40T 50T 70T Dimensions...
Страница 18: ...18 EN CDP 40T 50T 70T Mounting and installation instructions CDP T 1...
Страница 19: ...19 EN Mounting and installation instructions CDP T Continued CDP 40T 2a CDP 50T 2b CDP 70T 2c...
Страница 20: ...20 EN 3 Mounting and installation instructions CDP T Continued...
Страница 35: ...35 EN Overview Accessories Water heating coil for CDP dehumidifier...
Страница 50: ...50 EN Spare parts 1 4 5 6 7 15 10 14 20 19 22 13 12 8 24 23 26 16 21 11 17 18 9 3 2 27 28 25...