45
EN
Evaporator sensor fail
If evaporator sensor is defect, then “EVAP” code will be shown when pressing UP or DOWN
during screen shows Sensor fail code “SEnS”.
If Evaporator sensor ok, then no “EVAP” code shall be shown.
If no buttons pressed within 10 seconds then screen will show “SEnS” fail again.
It is not possible to enter menu setup to modify set point.
RH/T sensor fail
If RH/T sensor is defect, then “rh°t” code will be shown when pressing UP or DOWN during
screen shows Sensor fail code “SEnS”.
If RH/T sensor ok, then no “rh°t” code shall be shown.
If no buttons pressed within 10 seconds then screen will show “SEnS” fail again.
It is not possible to enter menu setup to modify set point.
Low pressure fail
Dehumidifier stopped because of Low Pressure detection.
Fail can not be dismissed from DRC1.
It is not possible to enter menu setup to modify set point.
Alarms continued
Press to see which sensor
is defect.
Press to see which sensor
is defect.
Press to see which sensor
is defect.
Press to see which sensor
is defect.