13
EN
Compressor control
The number of compressor starts is limited by a 6 minutes timer, which starts when the
compressor is switched on.
The timer must have come to an end before the compressor can be switched on again.
Each time the unit has been switched off on the main switch, by the built-in hygrostat or by
an external hygrostat, it will take 30 seconds before the unit can be switched on again.
This is a safety feature protecting the compressor against overloading caused by too high
pressure in the cooling circuit at start up.
Defrosting
This unit is equipped with an intelligent defrosting strategy.
The unit monitors the temperature of the evaporator, and when the temperature have been
below a certain temperature for a period of time, then the dehumidifier will switch to active
defrosting, the fans will stop, and the magnetic valve will open.
The hot gas can now pass through the evaporator.
When the evaporator have the right temperature again the magnet valve will close and the
dehumidification will continue.
Safety circuit
If the temperature in the dehumidifier increases to a temperature of more than 55 °C (in case
of fan failure or room air temperature higher than 36 °C), the compressor stops automatically to
avoid damaging it. When the temperature allows for it the dehumidification will continue.
Product and functional description -
continued
Содержание CDP 50
Страница 9: ...9...
Страница 14: ...14 EN CDP 40 50 70 CDP 40T 50T 70T Dimensions...
Страница 18: ...18 EN CDP 40T 50T 70T Mounting and installation instructions CDP T 1...
Страница 19: ...19 EN Mounting and installation instructions CDP T Continued CDP 40T 2a CDP 50T 2b CDP 70T 2c...
Страница 20: ...20 EN 3 Mounting and installation instructions CDP T Continued...
Страница 35: ...35 EN Overview Accessories Water heating coil for CDP dehumidifier...
Страница 50: ...50 EN Spare parts 1 4 5 6 7 15 10 14 20 19 22 13 12 8 24 23 26 16 21 11 17 18 9 3 2 27 28 25...