Set node ID and CAN bus Baudrate
1. Connect the USB-RS323 converter cable to the laptop.
2. Open the WS Wireless Configurator.
3. Connect to the device.
4. Select Read data from the device icon.
5. Select the node ID (set to 33 by default).
6. Select the CAN bus baud rate (set to 250 kb/s by default).
CAN receive
All CAN Messages with ID Length 11 bit or 29 bit are received by WS103 (objects #0 and #1 are active and
no mask and no down sampling are applied by default).