2. CONNECTION, SAFETY AND HANDLING

Instructions

This operating manual should be read carefully before installation and 

start-up of the substation. The manufacturer accepts no liability for 

damages or faults that result from non-compliance with the operating 

manual. Please read and follow all the instructions carefully to prevent 

accidents, injury and damage to property. The risk of persons being 

injured and equipment damaged increases considerably if the recom-

mended permissible operating parameters are exceeded. 

Installation, assembly work, first start-up and maintenance work may be 

carried out only by qualified and authorized personnel in compliance 

with the safety regulations (both heating and electrical work).

Energy source

The substation is designed for district heating as the primary source of 

energy. However, also other energy sources can be used where the ope-

rating conditions allow it and always are comparable to district heating.

Application

The substation is designed only to operate with water and other heating 

media may not be used.   

Connect the substation to the house piping in a frost-free room,  where 

the temperature does not exceed 50 °C and the humidity does not ex-

ceed 80%. Do not cover or wall up the substation or in any other way 

block the entrance to the station.

Choice of material

Choice of materials always in compliance with local legislation.

Corrosion protection

T

he risk of equipment corrosion increases considerably if recommended 

permissible chloride compounds are exceeded.

All pipes are made of min. AISI 304 (heating) and min. AISI 316 (domestic 

water) stainless steel as well as brass. Components for domestic water, 

however, primarily in dezincification-resistant brass. Heat exchangers 

are made of stainless steel and are copper-soldered or steel-soldered.

Surfaces in contact with water can be subject to two problems, limescale 

formation and corrosion.

The nature of the water will be of great importance in this context, where 

the pH value, chlorides, gases, etc., have a decisive effect on how much 

lime is deposited and how aggressive the water is.

The temperature also has a great influence in this context. For example 

the corrosion rate increases by a factor of 2 to 3 for every 10° C tem-

perature rise.

With knowledge of the chemical water composition and operating 

conditions of a heating system, the risk of scaling and corrosion can be 

assessed. Based on that, recommendations can be made to avoid scaling 

and/or corrosion problems in the components.

See item 19, page 43 for more detailed Guidelines for Water Quality in Dan-

foss brazed heat exchangers and recommended Chloride concentration 

to avoid Stress Corrosion Cracking.

Safety valve(s)

We recommend mounting of safety valve(s), however, always in com-

pliance with local regulations.

Noise level

≤ 55 dB

Storage and Handling

If thesubstation is stored before installation, make sure that the place is 

dry and heated. Humidity max. 80% and storage temperature 5-70 °C).

Do not stack the unit higher than factory shipped. Units that are shipped 

in cardboard packaging are to be lifted by the carrying handles of the 

packaging. Transport / removals over great distances should be carried 

out on pallets.

During and after unpacking, the water heater can be lifted by hand 

in the mounting plate. Note that lifting in the pipes can cause leaks. 

ALWAYS re-tighten.

Handling

When working on the water heater suitable safety shoes must be worn.

Connections

The substation must be equipped with features that ensure that the 

water heater can be separated from all energy sources (also power 

supply).

 

Warning of hot surfaces

Parts of the water heater may become hot and hot surfaces can 

cause serious burns. Please be extremely cautious in close proxi-mi-

ty to the water heater.

Warning of high pressure and high temperature

The stations work at a maximum supply temperature from the dis-

trict heating network of 120°C and the stations work with a operat-

ing pressure of 16 bar, which may put the user at risk of burns from 

touching the surface or from the emissions of hot media (water/

steam). The risk of persons being injured and equipment damaged 

increases considerably if the recommended permissible operating 

parameters are exceeded.

Emergency

In case of danger or accidents - fire, leaks or other dangerous circum-

stances - interrupt all energy sources to the station if possible, and 

seek expert help.

In case of discoloured or bad-smelling domestic hot water, close all  

shut-off valves on the water heater, inform the operating personnel 

and call for expert help immediately.

Warning of transport damage

Before water heater installation, please make sure that the water 

heater has not been damaged during transport. Always transport 

the water heater with the utmost care and caution.

IMPORTANT - Tightening of connections

Due to vibrations during transport all flange connections, screw 

joints and electrical clamp and screw connections must be check-ed 

and tightened before water is added to the system. After water has 

been added to the system and the system has been put into opera-

tion, re-tighten ALL connections. 

(Do not overstrain! - See page 

10, Test and connections

)

        

  

NOTE: 

Interventions/rework on our components results in loss of

warranty.

Montage- und Betriebsanleitung / User manual   

VXe SLS

Содержание VXe SLS

Страница 1: ...stem For indirect heating with storage loading system Indirekte Hausstation mit einem Heizkreis und Speicherladesystem im Prim rkreis For indirect heating with 1 HE circuit with primary connection for...

Страница 2: ...justment and commissioning 14 10 0 Heizkreis Danfoss ECL 310 Comfort Heating circuit Danfoss ECL 310 Comfort 15 11 0 Regelung des Heizkreises Control of heating circuit 17 12 0 Heizkreispumpe Heating...

Страница 3: ...n gegeben werden SiehePunkt19 Seite42 f rdetailliertereRichtlinienf rdieWasserqualit tin gel tetenDanfoss W rme bertragerunddieempfohleneChloridkonzentra tionzurVermeidungvonSpannungsrisskorrosion Sic...

Страница 4: ...e43formoredetailedGuidelinesforWaterQualityinDan foss brazed heat exchangers and recommended Chloride concentration to avoid Stress Corrosion Cracking Safety valve s We recommend mounting of safety va...

Страница 5: ...Sie das Produkt zur EntsorgunginEinzelteileundf hrenSiesiegem dengeltenden rtli chenVorschriften sortenrein der Entsorgung zu Reach All products of theVXe series comply with the provisions of the REA...

Страница 6: ...des Systems kann zu Leckagen f hren Aus diesem Grund kann es erforderlich sein die Anschl sse nach der Inbetriebnahme erneut festzuziehen Hinweis Heben Sie niemals die Station an ihrer Frontabdeckung...

Страница 7: ...changer HE 2 Plattenw rme bertrager TWW Plate heat exchanger DHW 5 Schmutzf nger Strainer 6 R ckschlagventil Non return valve 7 Kugelhahn Ball valve 8 Umw lzpumpe HE Circulation pump HE 9 Umw lzpumpe...

Страница 8: ...mensional reproduction of contents to be authorized by Danfoss Redan A S No PROTO 910 Rev Sheet 1 1 Designation PROTO 910 VXe Replace Design 18 01 2022 hms Approval Danfoss Redan A S Projection Scale...

Страница 9: ...rden Pr fen Sie nach der Erw rmung des Systems alle Anschl sse und ziehen Sie sie sofern er forderlich erneut fest Bitte beachten Sie dass die Anschl sse EPDM Dichtungen auf weisen k nnen Aus diesem G...

Страница 10: ...heating of the system check all the connections and retighten if necessary Please note that the connections may feature EPDM rubber gaskets Therefore it is important that you DO NOT OVERTIGHTEN the u...

Страница 11: ...vibrations and shocks during transport and handling may have caused leaks Once the system has been filled with water tighten all the pipe connections once more before performing pressure test for leak...

Страница 12: ...bis 1 5 mm Anschlu f r ECL 310 Schlie en Sie die Kabelenden and die gemeinsame Erdungsklemme 30 und Klemme 29 des ECL Reglers an Zugriff zum ECL Sockel Um den Regler aus dem Sockel auszubauen f r den...

Страница 13: ...connections The cables can be connected to the sensor in any order Connection cable 2 x 0 4 1 5 mm Connection for ECL 310 Connect the cable ends to ECL controller in common ground terminal and in term...

Страница 14: ...Hei zungsanlage nach evtl Leckagen untersucht werden und auch der Vordruck des Ausdehnungsgef es soll nachgepr ft werden General information PLEASE NOTE Some models may have a slightly different appea...

Страница 15: ...igieren indem Sie den Navigator nach links oder rechts in die gew nschte Position drehen Der Stellungsanzeiger im Display zeigt Ihnen an an welcher Stelle im Men Sie sich gerade befinden 3 DenNavigato...

Страница 16: ...1 Connect the controller and switch it on 2 Choose MENU in any circuit Confirm and turn the dial and choose Common controller settings in the circuit selector at the top right corner in the display Y...

Страница 17: ...t from factory In the event of operating disturbances the actuator can be shut off manually by turning the manual override knob on top of the actuator clockwise Please note that the knob can be tight...

Страница 18: ...enfeld wird Folgendes angezeigt Anzeigemodus w hrend des Betriebes Betriebsstatus Alarmstatus Einstellmodus nach Dr cken der Taste W hrend des Betriebs zeigt das Display den Betriebsstatus der Pumpe M...

Страница 19: ...r Taste f r mehr als 10 Sekunden aktiviert bzw deaktiviert werden Dabei leuchten die gelben LEDs kurz auf um anzuzeigen dass die Deaktivierung oder Aktivierung erfolgt ist F rweitereInformationen sieh...

Страница 20: ...iew during operation operation status alarm status settings view after pressing the button During operation the display shows the performance of the pump By pressing the button the display changes sta...

Страница 21: ...button down for more than 10 seconds LEDs will flash and the pump is unlocked To lock the pump repeat the procedure For more information se enclosed Grundfos in structions Alarm status In case the 1s...

Страница 22: ...gestalteten Kammer unterhalb des ECL Reglers montiert werden Danfoss ECL Comfort 310 Der Applikationsschl ssel enth lt Informationen ber die Applika tion Sprache und Werkseinstellungen angepasst an d...

Страница 23: ...filling piece for fitting of a heat meter Calculator of the heat meter can be mounted into a special cham ber that is designed for easy reading Danfoss ECL Comfort 310 The application Key contains in...

Страница 24: ...nn mit einem Sicherheitsthermostat gegen berhitzung ausgestattet werden Ab Werk ist der Jumo AT Sicherheitsthermostat mit dem Danfoss ECL Regler mit 2 m Kabel vorverdrahtet so dass derThermostat Ge h...

Страница 25: ...Jumo AT The DHW circuit can be supplied with a safety thermostat Jumo AT for protection against overheating From factory the Jumo AT safety thermostat is pre wired to the Danfoss ECL controller with a...

Страница 26: ...kseitig auf die maximale Wassermenge voll ge ffnet eingestellt Die Position der Kerbe in der Einstellschraube ist in L ngsrichtung des Ventils wie im Foto B angegeben Hinweis Bei der Erstinbetriebnahm...

Страница 27: ...limiter is factory set to the maximum water flow fully open The position of the notch in the adjusting screw is in the lon gitudinal direction of the valve as indicated in photo B Note The system medi...

Страница 28: ...hWartungsarbeiten Nach denWartungsarbeiten und vor dem Einschalten der Anlage Alle gel sten Schraubenverbindungen auf festen Sitz berpr fen berpr fen oballezuvorentferntenSchutzvorrichtungen Abdeckung...

Страница 29: ...Ifitbecomesnecessarytoclean the exchanger with acid this can be done as shown on the drawing to the right Brazed plate heat exchangers can withstand rinsing with a dilute acid solution e g 5 formic a...

Страница 30: ...nen ausgetauscht werden Pr fen Sie ob alle W rmed mmungs Abdeck ungen intakt sind Pr fen Sie ob die W rmed mmung das Produkt fest umschlie t Pr fen Sie ob die Temperaturregler gem den Anweisungen in d...

Страница 31: ...Montage und Betriebsanleitung User manual VXe SLS Danfoss Produced by Danfoss Redan A S 2022 03 31 AQ40514397064001 000101 145X2068...

Страница 32: ...sorgung in Ordnung ist Kontrollieren da sich im Pumpengeh use keine Luft befindet siehe Pumpenhandbuch Zapftemperatur zu niedrig Siehe bitte Kein warmes Wasser Siehe bitte Kein warmes Wasser R ckschla...

Страница 33: ...auchf hler austauchen Schwankende Temperatur R ckschlagventil der Zirkulationsleitung defekt f hrt zur Vermischung Zirkulationsleitung k hlt ab w hrend der Entnahme R ckschlagventil austauchen Tempera...

Страница 34: ...hot water Dirt strainer in the district heating supply line clogged Clean the dirt strainer Defective actuator or possibly dirt in the valve housing Check the functions of the actuator clean valve se...

Страница 35: ...alve on the circulation line defective leads to mixing and the circulation water pipes become cold during tapping Replace the non return valve Temperature falls during tapping lack of capacity Control...

Страница 36: ...sorgung der Pumpe funktioniert und dass sie sich drehen kann Pr fen ob Luft im Pumpengeh use eingeschlossen ist siehe Handbuch der Pumpe Die Pumpe ist auf eine zu geringe Dreh zahl eingestellt Pumpe a...

Страница 37: ...die Heizk rper im System unten zu heiss werden Es ist sehr wichtig die Temperatur im Vorlauf der Heizk rp er so gering wie m glich zu halten um eine angenehme Temperatur zu errichen Das System ist ein...

Страница 38: ...trapped in the pump housing see pump manual The pump is set at too low speed of rotation Set the pump at higher speed of rotation Air pockets in the system Vent the installation thoroughly Limiting o...

Страница 39: ...ining a reasonable level of comfort The system is single pipe loop Das System sollte mit elektronis chen Reglern und R cklauff hlern ausgestattet sein Pump pressure too high Pumpe niedriger einstellen...

Страница 40: ...40 Danfoss Produced by Danfoss Redan A S 2022 03 145X2068 AQ40514397064001 000101 17 EU KONFORMIT TSERKL RUNG EU DECLARATION OF CONFORMITY Montage und Betriebsanleitung User manual VXe SLS...

Страница 41: ...eiten f hren kann Der Hersteller bernimmt keine Haftung f r Leckagen die aus berspannung zur ckzuf hren sind Von dem Installateur auszuf llen Diese Anlage wurde nachgezogen angepasst und in Betrieb ge...

Страница 42: ...en nt tr ra at tiio on n AISI 316L W Nr 1 4404 Cu CuNi StS pH 6 0 o o 6 0 7 5 o o 7 5 10 5 10 5 o o Leitf higkeit S cm 10 10 500 500 1000 o 1000 o Freies Chlor mg l 0 5 0 5 1 o 1 5 o o o 5 Ammoniak NH...

Страница 43: ...o Hardness ratio Ca2 Mg2 HCO3 0 0 3 0 3 0 5 o 0 5 Good corrosion resistance o Corrosion could happen when more parameters are evaluated with o o Risk of corrosion Use is not recommended Hardness rati...

Страница 44: ...44 Danfoss Produced by Danfoss Redan A S 2022 03 145X2068 AQ40514397064001 000101...

Отзывы: