Voltage [V]
Power range
[kW (hp)]
Minimum waiting time
(minutes)
200–240
0.37–3.7 (0.5–5)
4
380–480
0.37–7.5 (0.5–10)
4
11–22 (15–30)
15
Table 2.1 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
•
Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
•
Ensure that only trained and qualified personnel
perform installation, start-up, and maintenance.
•
Ensure that electrical work conforms to national
and local electrical codes.
•
Follow the procedures in this guide.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
•
Ensure that all safety covers are in place and
securely fastened before applying power.
Safety
VLT
®
Midi Drive FC 280
8
Danfoss A/S © 10/2017 All rights reserved.
MG07A402
2
2