
3.6.3 Digital inputs - Terminal X30/1-4
Parameters for set-up: 5-16, 5-17 and 5-18
Number of digital
inputs
Voltage level
Voltage levels
Tolerance
Max. Input impedance
3
0-24 V DC
PNP type:
Common = 0 V
Logic “0”: Input < 5 V DC
Logic “0”: Input > 10 V DC
NPN type:
Common = 24 V
Logic “0”: Input > 19 V DC
Logic “0”: Input < 14 V DC
± 28 V continuous
± 37 V in minimum 10 sec.
Approx. 5 k ohm
3.6.4 Analog Voltage inputs - Terminal X30/10-12
Parameters for set-up: 6-3*, 6-4* and 16-76
Number of analog voltage inputs
Standardized input signal
Tolerance
Resolution
Max. Input impedance
2
0-10 V DC
± 20 V continuously
10 bits
Approx. 5 K ohm
3.6.5 Digital Outputs - Terminal X30/5-7
Parameters for set-up: 5-32 and 5-33
Number of digital outputs
Output level
Tolerance
Max.impedance
2
0 or 24 V DC
± 4 V
≥
600 ohm
3.6.6 Analog Outputs - Terminal X30/5+8
Parameters for set-up: 6-6* and 16-77
Number of analog outputs
Output signal level
Tolerance
Max.impedance
1
0/4 - 20 mA
± 0.1 mA
< 500 ohm
Automation VT Drive FC322 Design Guide
3 VLT Automation VT Drive Selection
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
81
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx