Data are measured according to IEC 60034-17.
Cable lengths are in metres.
FC322, P7K5T2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
230
0.13
0.510
3.090
50
230
0.23
2.034
100
230
0.54
0.580
0.865
150
230
0.66
0.560
0.674
FC322, P11KT2
Cable
length [m]
Mains
voltage [V]
Rise time [
μ
sec]
Vpeak
[kV]
dU/dt [kV/
μ
sec]
36
240
0.264
0.624
1.890
136
240
0.536
0.596
0.889
150
240
0.568
0.568
0.800
FC322, P15KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.556
0.650
0.935
100
240
0.592
0.594
0.802
150
240
0.708
0.587
0.663
FC322, P18KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.568
0.580
0.816
150
240
0.720
0.574
0.637
FC322, P22KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
240
0.244
0.608
1.993
136
240
0.568
0.580
0.816
150
240
0.720
0.574
0.637
FC322, P30KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
240
0.194
0.626
2.581
50
240
0.252
0.574
1.822
150
240
0.488
0.538
0.882
3 VLT Automation VT Drive Selection
Automation VT Drive FC322 Design Guide
68