FC322, P37KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.594
100
240
0.536
0.566
0.844
150
240
0.776
0.546
0.562
FC322, P45KT2
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
30
240
0.300
0.598
1.594
100
240
0.536
0.566
0.844
150
240
0.776
0.546
0.562
FC322, P1K5T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
690
0.640
0.690
0.862
50
985
0.470
0.985
150
1045
0.760
1.045
0.947
FC322, P4K0T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
400
0.172
0.890
4.156
50
400
0.310
2.564
150
400
0.370
1.190
1.770
FC322, P7K5T4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
5
500
0.04755
0.739
8.035
50
500
0.207
4.548
150
500
0.6742
1.030
2.828
FC322, P11KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
15
480
0.192
1.300
5.416
100
480
0.612
1.300
1.699
150
480
0.512
1.290
2.015
FC322, P15KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[
μ
sec]
Vpeak
[kV]
dU/dt
[kV/
μ
sec]
36
480
0.396
1.210
2.444
100
480
0.844
1.230
1.165
150
480
0.696
1.160
1.333
Automation VT Drive FC322 Design Guide
3 VLT Automation VT Drive Selection
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
69
3
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx