To read a text via the PWE block, set the parameter command (AK) to ’F’ Hex. The index character high-byte must be “4”.
Some parameters contain text that can be written to via the serial bus. To write a text via the PWE block, set the parameter command (AK) to ’F’ Hex.
The index characters high-byte must be “5”.
7.4.11 Data Types Supported by VLT Automation VT Drive
Data types
Description
3
Integer 16
4
Integer 32
5
Unsigned 8
6
Unsigned 16
7
Unsigned 32
9
Text string
10
Byte string
13
Time difference
33
Reserved
35
Bit sequence
Unsigned means that there is no operational sign in the telegram.
7.4.12 Conversion
The various attributes of each parameter are displayed in the section
Factory Settings. Parameter values are transferred as whole numbers
only. Conversion factors are therefore used to transfer decimals.
par. 4-12
Motor Speed Low Limit [Hz] has a conversion factor of 0.1.
To preset the minimum frequency to 10 Hz, transfer the value 100. A
conversion factor of 0.1 means that the value transferred is multiplied by
0.1. The value 100 is thus perceived as 10.0.
Conversion table
Conversion index
Conversion factor
74
0.1
2
100
1
10
0
1
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
-5
0.00001
7.4.13 Process Words (PCD)
The block of process words is divided into two blocks of 16 bits, which always occur in the defined sequence.
Automation VT Drive FC322 Design Guide
7 RS-485 Installation and Set-up
MG.20.X1.22 - VLT
®
is a registered Danfoss trademark
207
7