WARNING
UNINTENDED START!
When adjustable frequency drive is connected to AC line
power, the motor may start at any time. The adjustable
frequency drive, motor, and any driven equipment must be
in operational readiness. Failure to be in operational
readiness when the adjustable frequency drive is
connected to AC line power could result in death, serious
injury, equipment, or property damage.
4.2.1 Uploading Data to the LCP
1.
Press [OFF] to stop the motor before uploading
or downloading data.
2.
Go to
0-50 LCP Copy
.
3.
Press [OK].
4.
Select
All to
LCP.
5.
Press [OK]. A progress bar shows the uploading
process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.2.2 Downloading Data from the LCP
1.
Press [OFF] to stop the motor before uploading
or downloading data.
2.
Go to
0-50 LCP Copy
.
3.
Press [OK].
4.
Select
All from
LCP.
5.
Press [OK]. A progress bar shows the
downloading process.
6.
Press [Hand On] or [Auto On] to return to normal
operation.
4.3 Restoring Default Settings
CAUTION
Initialization restores the unit to factory default settings.
Any programming, motor data, localization, and
monitoring records will be lost. Uploading data to the LCP
provides a backup prior to initialization.
Restoring the adjustable frequency drive parameter
settings back to default values is done by initialization of
the adjustable frequency drive. Initialization can be
through
14-22 Operation Mode
or manually.
•
Initialization using
14-22 Operation Mode
does not
change adjustable frequency drive data such as
operating hours, serial communication selections,
personal menu settings, fault log, alarm log, and
other monitoring functions.
•
Using
14-22 Operation Mode
is generally
recommended.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
4.3.1 Recommended Initialization
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
14-22 Operation Mode
.
3.
Press [OK].
4.
Scroll to
Initialization
.
5.
Press [OK].
6.
Remove power to the unit and wait for the
display to turn off.
7.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
8.
Alarm 80 is displayed.
9.
Press [Reset] to return to operation mode.
4.3.2 Manual Initialization
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during
start-up. This may take slightly longer than normal.
Manual initialization does not reset the following
adjustable frequency drive information
•
15-00 Operating Hours
•
15-03 Power-ups
•
15-04 Over Temps
•
15-05 Over Volts
User Interface
VLT
®
AutomationDrive Instruction
Manual
4-4
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
4
4
Содержание VLT AutomationDrive FC 303
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300...
Страница 3: ...Safety VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 7: ...Contents VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG 33 AI 22 VLT is a registered Danfoss trademark 1 1...
Страница 29: ...Installation VLT AutomationDrive Instruction Manual 2 16 MG 33 AI 22 VLT is a registered Danfoss trademark 2 2...
Страница 101: ...Specifications VLT AutomationDrive Instruction Manual 10 26 MG 33 AI 22 VLT is a registered Danfoss trademark 10 10...
Страница 105: ...www danfoss com drives MG33AI22 130R0300 MG33AI22 Rev 2011 05 13...