![Danfoss VLT AutomationDrive FC 303 Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-303/vlt-automationdrive-fc-303_instruction-manual_3731801076.webp)
10 Specifications
10.1 Power-dependent Specifications
Line Power Supply 3 x 200–240V AC
FC 301/FC 302
PK25
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P3K7
Typical Shaft Output [kW]
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
3.7
Enclosure IP20/IP21
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure IP 20 (FC 301 only)
A1
A1
A1
A1
A1
A1
-
-
-
Enclosure IP 55, 66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous
(3 x 200–240V) [A]
1.8
2.4
3.5
4.6
6.6
7.5
10.6
12.5
16.7
Intermittent
(3 x 200–240V) [A]
2.9
3.8
5.6
7.4
10.6
12.0
17.0
20.0
26.7
Continuous
kVA (208V AC) [kVA]
0.65
0.86
1.26
1.66
2.38
2.70
3.82
4.50
6.00
Max. input current
Continuous
(3 x 200–240V) [A]
1.6
2.2
3.2
4.1
5.9
6.8
9.5
11.3
15.0
Intermittent
(3 x 200–240V) [A]
2.6
3.5
5.1
6.6
9.4
10.9
15.2
18.1
24.0
Additional specifications
Max. cable size (line power, motor,
brake) [mm
2
(AWG
2)
)]
0.2–4 (24–10)
Estimated power loss
at rated max. load [W]
4)
21
29
42
54
63
82
116
155
185
Weight, enclosure IP20 [kg]
4.7
4.7
4.8
4.8
4.9
4.9
4.9
6.6
6.6
A1 (IP20)
2.7
2.7
2.7
2.7
2.7
2.7
-
-
-
A5 (IP 55, 66)
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
13.5
Efficiency
4)
0.94
0.94
0.95
0.95
0.96
0.96
0.96
0.96
0.96
0.25–3.7 kW only available as 160% high overload.
Line Power Supply 3 x 200–240V AC
FC 301/FC 302
P5K5
P7K5
P11K
High/ Normal Load
1)
HO
NO
HO
NO
HO
NO
Typical Shaft Output [kW]
5.5
7.5
7.5
11
11
15
Enclosure IP20
B3
B3
B4
Enclosure IP21
B1
B1
B2
Enclosure IP55, 66
B1
B1
B2
Output current
Continuous
(3 x 200–240V) [A]
24.2
30.8
30.8
46.2
46.2
59.4
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
38.7
33.9
49.3
50.8
73.9
65.3
Continuous
kVA (208V AC) [kVA]
8.7
11.1
11.1
16.6
16.6
21.4
Max. input current
Continuous
(3 x 200–240V) [A]
22
28
28
42
42
54
Intermittent
(60 sec overload)
(3 x 200–240V) [A]
35.2
30.8
44.8
46.2
67.2
59.4
Additional specifications
Max. cable size [mm
2
(AWG)]
2)
16 (6)
16 (6)
35 (2)
Max cable size with line power disconnect
16 (6)
Estimated power loss
at rated max. load [W]
4)
239
310
371
514
463
602
Weight,
enclosure IP21, IP55, 66 [kg]
23
23
27
Efficiency
4)
0.964
0.959
0.964
Specifications
VLT
®
AutomationDrive Instruction
Manual
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
10-1
10
10
Содержание VLT AutomationDrive FC 303
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300...
Страница 3: ...Safety VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 7: ...Contents VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG 33 AI 22 VLT is a registered Danfoss trademark 1 1...
Страница 29: ...Installation VLT AutomationDrive Instruction Manual 2 16 MG 33 AI 22 VLT is a registered Danfoss trademark 2 2...
Страница 101: ...Specifications VLT AutomationDrive Instruction Manual 10 26 MG 33 AI 22 VLT is a registered Danfoss trademark 10 10...
Страница 105: ...www danfoss com drives MG33AI22 130R0300 MG33AI22 Rev 2011 05 13...