Control card, RS-485 serial communication:
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB ground connection is not galvanically isolated from protection ground. Use only an isolated laptop as PC connection to
the USB connector on the adjustable frequency drive.
Relay outputs:
Programmable relay outputs
FC 301all kW: 1 / FC 302 all kW: 2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
240V AC, 2A
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
60V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load)
24 V DC, 0.1A
Relay 02 (FC 302 only) Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
Overvoltage cat. II
400V AC, 2A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cos
φ
0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
80V DC, 2A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
240V AC, 2A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cos
φ
0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load)
50V DC, 2A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
24 V DC, 0.1A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300V AC2A
Cable lengths and cross-sections for control cables
1)
:
Max. motor cable length, shielded
FC 301: 164 ft [50 m]/FC 301 (A1): 82 ft [25 m]/ FC 302: 492 ft [150 m]
Max. motor cable length, non-shielded
FC 301: 246 ft [75 m]/FC 301 (A1): 164 ft [50 m]/ FC 302: 984 ft [300 m]
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
0.0023 in
2
[1.5mm
2
]/ 16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves
0.0016 in
2
[1 mm
2
]/ 18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
0.0008 in
2
[0.5mm
2
]/ 20 AWG
Minimum cross-section to control terminals
0.00039 in
2
[0.25mm
2
]/ 24AWG
1)
Power cables, see tables in 10.1 Power-dependent Specifications.
Control card performance:
Scan interval
FC 301: 5 ms / FC 302: 1 ms
Control characteristics:
Resolution of output frequency at 0–1000Hz
±
0.003Hz
Repeat accuracy of
Precise start/stop
(terminals 18, 19)
≤±
0.1msec
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2ms
Speed control range (open-loop)
1:100 of synchronous speed
Speed control range (closed-loop)
1:1000 of synchronous speed
Specifications
VLT
®
AutomationDrive Instruction
Manual
10-14
MG.33.AI.22 - VLT
®
is a registered Danfoss trademark
10
10
Содержание VLT AutomationDrive FC 303
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300...
Страница 3: ...Safety VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 7: ...Contents VLT AutomationDrive Instruction Manual MG 33 AI 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG 33 AI 22 VLT is a registered Danfoss trademark 1 1...
Страница 29: ...Installation VLT AutomationDrive Instruction Manual 2 16 MG 33 AI 22 VLT is a registered Danfoss trademark 2 2...
Страница 101: ...Specifications VLT AutomationDrive Instruction Manual 10 26 MG 33 AI 22 VLT is a registered Danfoss trademark 10 10...
Страница 105: ...www danfoss com drives MG33AI22 130R0300 MG33AI22 Rev 2011 05 13...