Relay outputs
Programmable relay outputs
FC 301 all kW: 1/FC 302 all kW: 2
Relay 01 terminal number
1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)
1)
on 1–3 (NC), 1–2 (NO) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
(inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 1–2 (NO), 1–3 (NC) (resistive load)
60 V DC, 1 A
Maximum terminal load (DC-13)
1)
(inductive load)
24 V DC, 0.1 A
Relay 02 (FC 302 only) terminal number
4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)
1)
on 4–5 (NO) (resistive load)
2)
,
3)
overvoltage cat. II
400 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–5 (NO) (inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–5 (NO) (resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–5 (NO) (inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
1)
on 4–6 (NC) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–6 (NC) (inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–6 (NC) (resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–6 (NC) (inductive load)
24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO)
24 V DC 1 mA, 24 V AC 20 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II.
3) UL applications 300 V AC 2 A.
Control card performance
Scan interval
1 ms
Control characteristics
Resolution of output frequency at 0–590 Hz
±
0.003 Hz
Repeat accuracy of precise start/stop (terminals 18, 19)
≤±
0.1 ms
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2 ms
Speed control range (open loop)
1:100 of synchronous speed
Speed control range (closed loop)
1:1000 of synchronous speed
Speed accuracy (open loop)
30–4000 RPM: Error
±
8 RPM
Speed accuracy (closed loop), depending on resolution of feedback device
0–6000 RPM: Error
±
0.15 RPM
Torque control accuracy (speed feedback)
Maximum error
±
5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor.
Specifications
Operating Guide
MG33AT02