8 Specifications
8.1 Electrical Data
8.1.1 Mains Supply 200–240 V
Type designation
PK25
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P3K7
Typical shaft output [kW/(hp)], high overload
0.25
(0.34)
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
3.0
(4.0)
3.7
(5.0)
Enclosure protection rating IP20 (FC 301 only)
A1
A1
A1
A1
A1
A1
–
–
–
Enclosure protection rating IP20, IP21
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure protection rating IP55, IP66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous (200–240 V) [A]
1.8
2.4
3.5
4.6
6.6
7.5
10.6
12.5
16.7
Intermittent (200–240 V) [A]
2.9
3.8
5.6
7.4
10.6
12.0
17.0
20.0
26.7
Continuous kVA (208 V) [kVA]
0.65
0.86
1.26
1.66
2.38
2.70
3.82
4.50
6.00
Maximum input current
Continuous (200–240 V) [A]
1.6
2.2
3.2
4.1
5.9
6.8
9.5
11.3
15.0
Intermittent (200–240 V) [A]
2.6
3.5
5.1
6.6
9.4
10.9
15.2
18.1
24.0
Additional specifications
Maximum cable cross-section
2),5)
for mains,
motor, brake, and load sharing [mm
2
] ([AWG])
4, 4, 4 (12,12,12)
(minimum 0.2 (24))
Maximum cable cross-section
2),5)
for disconnect
[mm
2
] ([AWG])
6, 4, 4 (10,12,12)
Estimated power loss at rated maximum load
[W]
3)
21
29
42
54
63
82
116
155
185
Efficiency
4)
0.94
0.94
0.95
0.95
0.96
0.96
0.96
0.96
0.96
Table 8.1 Mains Supply 200–240 V, PK25–P3K7
Type designation
P5K5
P7K5
P11K
High/normal overload
1)
HO
NO
HO
NO
HO
NO
Typical shaft output [kW/(hp)]
5.5 (7.5)
7.5 (10)
7.5 (10)
11 (15)
11 (15)
15 (20)
Enclosure protection rating IP20
B3
B3
B4
Enclosure protection rating IP21, IP55, IP66
B1
B1
B2
Output current
Continuous (200–240 V) [A]
24.2
30.8
30.8
46.2
46.2
59.4
Intermittent (60 s overload) (200–240 V) [A]
38.7
33.9
49.3
50.8
73.9
65.3
Continuous kVA (208 V) [kVA]
8.7
11.1
11.1
16.6
16.6
21.4
Maximum input current
Continuous (200–240 V) [A]
22.0
28.0
28.0
42.0
42.0
54.0
Intermittent (60 s overload) (200–240 V) [A]
35.2
30.8
44.8
46.2
67.2
59.4
Additional specifications
IP20 maximum cable cross-section
2),5)
for mains, brake, motor, and
load sharing [mm
2
] ([AWG])
10, 10,- (8, 8,-)
10, 10,- (8, 8,-)
35,-,- (2,-,-)
IP21 maximum cable cross-section
2),5)
for mains, brake, and load
sharing [mm
2
] ([AWG])
16,10,16 (6, 8, 6)
16,10,16 (6, 8, 6)
35,-,- (2,-,-)
IP21 maximum cable cross-section
2),5)
for motor [mm
2
] ([AWG])
10, 10,- (8, 8,-)
10, 10,- (8, 8,-)
35,25,25 (2, 4, 4)
Maximum cable cross-section
2),5)
for disconnect [mm
2
] ([AWG])
16,10,10 (6, 8, 8)
Estimated power loss at rated maximum load [W]
3)
239
310
371
514
463
602
Efficiency
4)
0.96
0.96
0.96
Table 8.2 Mains Supply 200–240 V, P5K5–P11K
Specifications
VLT
®
AutomationDrive FC 301/302
32
Danfoss A/S © 05/2018 All rights reserved.
MG33AT02
8