![Danfoss VLT AutomationDrive FC 301 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-301/vlt-automationdrive-fc-301_operating-manual_3414831036.webp)
8.1.2 Mains Supply 380–500 V
Type designation
PK37
PK55
PK75
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Typical shaft output [kW/(hp)], high overload
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
3.0
(4.0)
4.0
(5.0)
5.5
(7.5)
7.5
(10)
Enclosure protection rating IP20 (FC 301 only)
A1
A1
A1
A1
A1
–
–
–
–
–
Enclosure protection rating IP20, IP21
A2
A2
A2
A2
A2
A2
A2
A2
A3
A3
Enclosure protection rating IP55, IP66
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A5
A5
Output current high overload 160% for 1 minute
Shaft output [kW/(hp)]
0.37
(0.5)
0.55
(0.75)
0.75
(1.0)
1.1
(1.5)
1.5
(2.0)
2.2
(3.0)
3.0
(4.0)
4.0
(5.0)
5.5
(7.5)
7.5
(10)
Continuous (380–440 V) [A]
1.3
1.8
2.4
3.0
4.1
5.6
7.2
10
13
16
Intermittent (380–440 V) [A]
2.1
2.9
3.8
4.8
6.6
9.0
11.5
16
20.8
25.6
Continuous (441–500 V) [A]
1.2
1.6
2.1
2.7
3.4
4.8
6.3
8.2
11
14.5
Intermittent (441–500 V) [A]
1.9
2.6
3.4
4.3
5.4
7.7
10.1
13.1
17.6
23.2
Continuous kVA (400 V) [kVA]
0.9
1.3
1.7
2.1
2.8
3.9
5.0
6.9
9.0
11
Continuous kVA (460 V) [kVA]
0.9
1.3
1.7
2.4
2.7
3.8
5.0
6.5
8.8
11.6
Maximum input current
Continuous (380–440 V) [A]
1.2
1.6
2.2
2.7
3.7
5.0
6.5
9.0
11.7
14.4
Intermittent (380–440 V) [A]
1.9
2.6
3.5
4.3
5.9
8.0
10.4
14.4
18.7
23
Continuous (441–500 V) [A]
1.0
1.4
1.9
2.7
3.1
4.3
5.7
7.4
9.9
13
Intermittent (441–500 V) [A]
1.6
2.2
3.0
4.3
5.0
6.9
9.1
11.8
15.8
20.8
Additional specifications
IP20, IP21 maximum cable cross-section
2),5)
for
mains, motor, brake, and load sharing [mm
2
]
([AWG])
4, 4, 4 (12,12,12)
(minimum 0.2(24))
IP55, IP66 maximum cable cross-section
2),5)
for
mains, motor, brake, and load sharing [mm
2
]
([AWG])
4, 4, 4 (12,12,12)
Maximum cable cross-section
2),5)
for disconnect
[mm
2
] ([AWG])
6, 4, 4 (10,12,12)
Estimated power loss at rated maximum load
[W]
3)
35
42
46
58
62
88
116
124
187
255
Efficiency
4)
0.93
0.95
0.96
0.96
0.97
0.97
0.97
0.97
0.97
0.97
Table 8.4 Mains Supply 380–500 V (FC 302), 380–480 V (FC 301), PK37–P7K5
Specifications
VLT
®
AutomationDrive FC 301/302
34
Danfoss A/S © 05/2018 All rights reserved.
MG33AT02
8
8