525–600 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker
Moeller
Maximum trip level
[A]
A2
0-75-4.0
gG-10
gG-25
PKZM0-25
25
A3
5.5–7.5
gG-10 (5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
A5
0.75–7.5
gG-10 (0.75–5.5)
gG-16 (7.5)
gG-32
PKZM0-25
25
B1
11–18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
gG-80
PKZM4-63
63
B2
22–30
gG-50 (22)
gG-63 (30)
gG-100
NZMB1-A100
100
B3
11–15
gG-25 (11)
gG-32 (15)
gG-63
PKZM4-50
50
B4
18.5–30
gG-40 (18.5)
gG-50 (22)
gG-63 (30)
gG-125
NZMB1-A100
100
C1
37–55
gG-63 (37)
gG-100 (45)
aR-160 (55)
gG-160 (37–45)
aR-250 (55)
NZMB2-A200
160
C2
75
aR-200 (75)
aR-250
NZMB2-A250
250
C3
37–45
gG-63 (37)
gG-100 (45)
gG-150
NZMB2-A200
150
C4
55–75
aR-160 (55)
aR-200 (75)
aR-250
NZMB2-A250
250
Table 8.15 525–600 V, Enclosure Types A, B, and C
525–690 V
Enclosure
Power [kW]
Recommended
fuse size
Recommended
maximum fuse
Recommended circuit
breaker
Moeller
Maximum trip level
[A]
A3
1.1
1.5
2.2
3
4
5.5
7.5
gG-6
gG-6
gG-6
gG-10
gG-10
gG-16
gG-16
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
gG-25
PKZM0-16
16
B2/B4
11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63
–
–
B4/C2
30
gG-63 (30)
gG-80 (30)
–
–
C2/C3
37
45
gG-63 (37)
gG-80 (45)
gG-100 (37)
gG-125 (45)
–
–
C2
55
75
gG-100 (55)
gG-125 (75)
gG-160 (55–75)
–
–
Table 8.16 525–690 V, Enclosure Types A, B, and C
Specifications
Operating Instructions
MG33AQ02
Danfoss A/S © 07/2015 All rights reserved.
67