Control card, RS485 serial communication
Terminal number
68 (P, TX+, RX+), 69 (N, TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Control card, USB serial communication
USB standard
1.1 (Full speed)
USB plug
USB type B plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high voltage terminals.
The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to
the USB connector on the frequency converter.
Relay outputs
Programmable relay outputs
FC 301 all kW: 1/FC 302 all kW: 2
Relay 01 terminal number
1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)
1)
on 1–3 (NC), 1–2 (NO) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
(inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 1–2 (NO), 1–3 (NC) (resistive load)
60 V DC, 1 A
Maximum terminal load (DC-13)
1)
(inductive load)
24 V DC, 0.1 A
Relay 02 (FC 302 only) terminal number
4–6 (break), 4–5 (make)
Maximum terminal load (AC-1)
1)
on 4–5 (NO) (resistive load)
2)3)
overvoltage cat. II
400 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–5 (NO) (inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–5 (NO) (resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–5 (NO) (inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
1)
on 4–6 (NC) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
1)
on 4–6 (NC) (inductive load
@
cos
φ
0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
1)
on 4–6 (NC) (resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
1)
on 4–6 (NC) (inductive load)
24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO), 4–6 (NC), 4–5 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II.
3) UL applications 300 V AC2A.
Control card performance
Scan interval
1 ms
Control characteristics
Resolution of output frequency at 0–590 Hz
±
0.003 Hz
Repeat accuracy of precise start/stop (terminals 18, 19)
≤±
0.1 ms
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2 ms
Speed control range (open loop)
1:100 of synchronous speed
Speed control range (closed loop)
1:1000 of synchronous speed
Speed accuracy (open loop)
30–4000 RPM: Error
±
8 RPM
Speed accuracy (closed loop), depending on resolution of feedback device
0–6000 RPM: Error
±
0.15 RPM
Torque control accuracy (speed feedback)
Maximum error
±
5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Specifications
VLT
®
AutomationDrive FC 301/302
64
Danfoss A/S © 07/2015 All rights reserved.
MG33AQ02
8