130BD529.12
1
2
3
4
5
6
7
8
9
L1
L2
L3
PE
10
11
PE
u
v
w
1
PLC
7
Motor, 3-phase and PE (screened)
2
Frequency converter
8
Mains, 3-phase and reinforced PE (not screened)
3
Output contactor
9
Control wiring (screened)
4
Cable clamp
10
Potential equalisation minimum 16 mm
2
(0.025 in
2
)
5
Cable insulation (stripped)
11
Clearance between control cable, motor cable and mains cable:
Minimum 200 mm (7.9 in)
6
Cable gland
Illustration 4.2 EMC-compliant Electrical Connection
For more information about EMC, see
chapter 4.2 EMC-compliant Installation
Electrical Installation
Operating Instructions
MG33AQ02
Danfoss A/S © 07/2015 All rights reserved.
15
4
4
Содержание VLT AutomationDrive FC 301
Страница 2: ......