12 13 18 19 27 29 32 33 20 37
39 42 50 53 54 55
61 68 69
130BB931.10
1
2
3
Illustration 4.8 Terminal Numbers
•
Connector 1 provides 4 programmable digital
inputs terminals, 2 additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage. FC
302 and FC 301 (optional in A1 enclosure) also
provide a digital input for STO function.
•
Connector 2 terminals (+)68 and (-)69 for RS485
serial communication connection.
•
Connector 3 provides 2 analog inputs, 1 analog
output, 10 V DC supply voltage, and commons
for the inputs and output.
•
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software.
Terminal description
Terminal
Parameter
Default
setting
Description
Digital inputs/outputs
12, 13
–
+24 V DC
24 V DC supply
voltage for digital
inputs and external
transducers. Maximum
output current 200
mA (130 mA for FC
301) for all 24 V loads.
18
5-10
[8] Start
Digital inputs.
19
5-11
[10] Reversing
32
5-14
[0] No
operation
33
5-15
[0] No
operation
27
5-12
[2] Coast
inverse
For digital input or
output. Default setting
is input.
29
5-13
[14] JOG
20
–
–
Common for digital
inputs and 0 V
potential for 24 V
supply.
37
–
STO
Safe input.
Analog inputs/outputs
39
–
Common for analog
output
Terminal description
Terminal
Parameter
Default
setting
Description
42
6-50
[0] No
operation
Programmable analog
output. 0–20 mA or
4–20 mA at a
maximum of 500
Ω
.
50
–
+10 V DC
10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum.
53
6-1*
Reference
Analog input. For
voltage or current.
Switches A53 and A54
select mA or V.
54
6-2*
Feedback
55
–
–
Common for analog
input.
Table 4.2 Terminal Description, Digital Inputs/Outputs, Analog
Inputs/Outputs
Terminal description
Terminal
Parameter
Default
setting
Description
Serial communication
61
–
–
Integrated RC-filter for
cable screen. ONLY for
connecting the screen
in the event of EMC
problems.
68 (+)
8-3*
–
RS485 interface. A
control card switch is
provided for
termination resistance.
69 (-)
8-3*
–
Relays
01, 02, 03
5-40 [0]
[0] No
operation
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
04, 05, 06
5-40 [1]
[0] No
operation
Table 4.3 Terminal Description, Serial Communication
Additional terminal
•
2 form C relay outputs. The location of the
outputs depends on the frequency converter
configuration.
•
Terminals located on built-in optional equipment.
See the manual provided with the equipment
option.
Electrical Installation
VLT
®
AutomationDrive FC 301/302
18
Danfoss A/S © 07/2015 All rights reserved.
MG33AQ02