Recommended initialisation procedure, via
parameter 14-22 Operation Mode
1.
Press [Main Menu] twice to access parameters.
2.
Scroll to
parameter 14-22 Operation Mode
and
press [OK].
3.
Scroll to
[2] Initialisation
and press [OK].
4.
Remove power to the unit and wait for the
display to turn off.
5.
Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
6.
Alarm 80, Drive initialised to default value
is
showed.
7.
Press [Reset] to return to operation mode.
Manual initialisation procedure
1.
Remove power to the unit and wait for the
display to turn off.
2.
Press and hold [Status], [Main Menu], and [OK] at
the same time while applying power to the unit
(approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during
start-up. This may take slightly longer than usual.
Manual initialisation does not reset the following frequency
converter information:
•
Parameter 15-00 Operating hours
.
•
Parameter 15-03 Power Up's
.
•
Parameter 15-04 Over Temp's
.
•
Parameter 15-05 Over Volt's
.
5.4 Basic Programming
5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic
motor and application parameters.
•
SmartStart starts automatically at first power-up
or after initialisation of the frequency converter.
•
Follow the on-screen instructions to complete the
commissioning of the frequency converter.
Always reactivate SmartStart by selecting
Quick
Menu Q4 - SmartStart
.
•
For commissioning without use of the SmartStart
wizard, refer to
chapter 5.4.2 Commissioning via
or the programming guide.
NOTICE
Motor data is required for the SmartStart set-up. The
required data is normally available on the motor
nameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-
up and check-out purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
1.
Press [Main Menu] on the LCP.
2.
Press the navigation keys to scroll to parameter
group
0-** Operation/Display
and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main Menu
Illustration 5.2 Main Menu
3.
Press the navigation keys to scroll to parameter
group
0-0* Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Illustration 5.3 Operation/Display
4.
Press the navigation keys to scroll to
parameter 0-03 Regional Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Illustration 5.4 Basic Settings
5.
Press the navigation keys to select
[0] Interna-
tional
or
[1] North America
as appropriate and
Commissioning
Operating Instructions