5 Specifications
5.1 Ambient Conditions
5.1.1 Environment
Enclosure
IP20/Chassis, IP54/NEMA 12, IP66/Type 4X
Vibration test
1.0 g
Maximum THDv
10%
Maximum relative humidity
5–93 (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
Class Kd
Ambient temperature
Maximum 122 °F (24-hour average maximum 113 °F)
Minimum ambient temperature during full-scale operation
32 °F
Minimum ambient temperature at reduced speed performance
14 °F
Temperature during storage/transport
-13 to +149/158 °F
Maximum altitude above sea level without derating
3280 ft
EMC standards, Emission
EN 61800-3
EMC standards, Immunity
EN 61800-3
Energy efficiency class
(1)
IE2
1
Determined according to IEC 61800-9-2 and EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
5.2 Mains Supply
Supply terminals (6-pulse)
L1, L2, L3
Supply voltage
(1)(2)
200–240 V ±10%
Supply voltage
(1)(2)
380–500 V ±10%
Supply voltage
(1)(2)
525–600 V ±10%
Supply voltage
(1)(2)
575–690 V ±10%
Supply frequency
47.5–63 Hz
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos φ)
Near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) ≤10 hp
Maximum twice per minute
Switching on input supply L1, L2, L3 (power-ups) 15–100 hp
Maximum once per minute
Switching on input supply L1, L2, L3 (power-ups) ≥125 hp
Maximum once per 2 minutes
Environment according to EN60664-1
Overvoltage category III/pollution degree 2
1
Mains voltage low/mains dropout: During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the
minimum stop level, which typically corresponds to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expec-
ted at mains voltage lower than 10% below the drive's lowest rated supply voltage.
2
The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/500/600 V maximum.
5.3 Control Input/Output and Control Data
5.3.1 Digital Inputs
Programmable digital inputs
4 (6)
(1)
AN354546796134en-000201 / 130R0954
30 | Danfoss A/S © 2021.05
Specifications
VLT®AutomationDrive EZ FC 321
Installation Guide
Содержание VLT AutomationDrive EZ FC 321
Страница 1: ...Installation Guide VLT AutomationDrive EZ FC 321 0 33 200 hp vlt drives danfoss com ...
Страница 2: ......