Table 18: Recommended Maximum UL Fuse Class, Voltage Range 3x200–240 V, Enclosure Sizes A, B, and C
Class fuses
Semiconductor fuses
Power [hp]
RK1/J/T [A]
CC [A]
SIBA
Littelfuse
Ferraz Shawmut (Mersen)
Bussmann (Eaton)
0.34–0.5
5
5
5017906-005
–
–
FWX-5
0.75–1.5
10
10
5017906-010
–
–
FWX-10
2.0
15
15
5017906-016
–
–
FWX-15
3.0
20
20
5017906-020
–
–
FWX-20
4.0
25
25
5017906-025
–
–
FWX-25
5.0
30
30
5012406-032
–
–
FWX-30
7.5
50
–
5014006-050
–
–
FWX-50
10
60
–
5014006-063
–
–
FWX-60
15
80
–
5014006-080
–
–
FWX-80
20–25
125
–
2028220-125
–
–
FWX-125
30
150
–
2028220-150
L25S-150
A25X-150
FWX-150
40
200
–
2028220-200
L25S-200
A25X-200
FWX-200
50
250
–
2028220-250
L25S-250
A25X-250
FWX-250
Table 19: Recommended Maximum UL Fuse Class, Voltage Range 380–500 V, Enclosure Sizes A, B, and C
Class fuses
Semiconductor fuses
Power [hp]
RK1/J/T [A]
CC [A]
SIBA
Littelfuse
Ferraz Shawmut (Mersen)
Bussmann (Eaton)
0.5–1.5
6
6
5017906-006
–
–
FWH-6
2.0–3.0
10
10
5017906-010
–
–
FWH-10
4.0
15
15
5017906-016
–
–
FWH-15
5.0
20
20
5017906-020
–
–
FWH-20
7.5
25
25
5017906-025
–
–
FWH-25
10
30
30
5012406-032
–
–
FWH-30
15
40
–
5014006-040
–
–
FWH-40
20
50
–
5014006-050
–
–
FWH-50
25
60
–
5014006-063
–
–
FWH-60
30
80
–
2028220-100
–
–
FWH-80
40
100
–
2028220-125
–
–
FWH-100
50
125
–
2028220-125
–
–
FWH-125
60
150
–
2028220-160
–
–
FWH-150
75
200
–
2028220-200
L50-S-225
A50-P-225
FWH-200
100
250
–
2028220-250
L50-S-250
A50-P-250
FWH-250
AN354546796134en-000201 / 130R0954 | 27
Danfoss A/S © 2021.05
Electrical Installation
VLT®AutomationDrive EZ FC 321
Installation Guide
Содержание VLT AutomationDrive EZ FC 321
Страница 1: ...Installation Guide VLT AutomationDrive EZ FC 321 0 33 200 hp vlt drives danfoss com ...