2.1.2 Caution
The frequency converter DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard,
disconnect the frequency converter from the mains before carrying out maintenance. Wait at least as follows before doing service on
the frequency converter:
Voltage (V)
Min. Waiting Time (Minutes)
4
15
20
30
40
200 - 240
0.25 - 3.7 kW
5.5 - 45 kW
380 - 480
0.37 - 7.5 kW
11 - 90 kW
110 - 250 kW
315 - 1000 kW
525-600
0.75 kW - 7.5 kW
11 - 90 kW
315 - 1200 kW
525-690
11 - 90 kW
45 - 400 kW
450 - 1200 kW
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
2.1.3 Disposal Instruction
Equipment containing electrical components may not be disposed of together with domestic
waste.
It must be separately collected with electrical and electronic waste according to local and cur-
rently valid legislation.
2.2 Software Version
2.2.1 Software Version and Approvals
VLT AQUA Drive
Software version: 1.33
This manual can be used with all VLT AQUA Drive frequency converters with software version 1.33.
The software version number can be found in parameter 15-43.
2 Introduction to VLT AQUA Drive
VLT
®
AQUA Drive Design Guide
12
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
2
Содержание VLT AQUA Drive Series
Страница 38: ...3 VLT AQUA Selection VLT AQUA Drive Design Guide 38 MG 20 N5 02 VLT is a registered Danfoss trademark 3...
Страница 106: ...5 How to Install VLT AQUA Drive Design Guide 106 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 150: ...5 How to Install VLT AQUA Drive Design Guide 150 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 168: ...7 RS 485 Installation and Set up VLT AQUA Drive Design Guide 168 MG 20 N5 02 VLT is a registered Danfoss trademark 7...
Страница 194: ...8 Troubleshooting VLT AQUA Drive Design Guide 194 MG 20 N5 02 VLT is a registered Danfoss trademark 8...