3 x Analog inputs
Operating range
Resolution
Accuracy
Sampling
Max load
Impedance
Used as
temperature
sensor input
-50 to +150 °C
11 bits
-50 °C
±1 Kelvin
+150 °C
±2 Kelvin
3 Hz
-
-
Used as
voltage input
0 - 10 VDC
10 bits
0.2% of full
scale at cal.
temperature
2.4 Hz
+/- 20 V
continuously
Approximately
5 k
Ω
When used for voltage, analog inputs are scalable by parameters for each input.
When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span.
When analog inputs are used for temperature sensors, it is possible to read out feedback value in both
°
C and
°
F.
When operating with temperature sensors, maximum cable length to connect sensors is 80 m non-screened / non-twisted wires.
Analog outputs - terminal X42/7-12
Parameter group for read out and write: 18-3*. See also
Programming Guide
Parameter groups for set-up: 26-4*, 26-5* and 26-6*. See also
Programming Guide
3 x Analog outputs
Output signal level
Resolution
Linearity
Max load
Volt
0-10 VDC
11 bits
1% of full scale
1 mA
Analog outputs are scalable by parameters for each output.
The function assigned is selectable via a parameter and have same options as for analog outputs on control card.
For a more detailed description of parameters, please refer to the
Programming Guide
.
Real-time clock (RTC) with back-up
The data format of RTC includes year, month, date, hour, minutes and weekday.
Accuracy of clock is better than
±
20 ppm at 25
°
C.
The built-in lithium back-up battery lasts on average for minimum 0 years, when frequency converter is operating at 40
°
C ambient temperature. If battery
pack back-up fails, analog I/O option must be exchanged.
3 VLT AQUA Selection
VLT
®
AQUA Drive Design Guide
74
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
3
Содержание VLT AQUA Drive Series
Страница 38: ...3 VLT AQUA Selection VLT AQUA Drive Design Guide 38 MG 20 N5 02 VLT is a registered Danfoss trademark 3...
Страница 106: ...5 How to Install VLT AQUA Drive Design Guide 106 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 150: ...5 How to Install VLT AQUA Drive Design Guide 150 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 168: ...7 RS 485 Installation and Set up VLT AQUA Drive Design Guide 168 MG 20 N5 02 VLT is a registered Danfoss trademark 7...
Страница 194: ...8 Troubleshooting VLT AQUA Drive Design Guide 194 MG 20 N5 02 VLT is a registered Danfoss trademark 8...