Illustration 3.23: Principle diagram for Analog I/O mounted in frequency converter.
Analog I/O configuration
3 x Analog Inputs, capable of handling following:
•
0 - 10 VDC
OR
•
0-20 mA (voltage input 0-10V) by mounting a 510
Ω
resistor across terminals (see NB!)
•
4-20 mA (voltage input 2-10V) by mounting a 510
Ω
resistor across terminals (see NB)
•
Ni1000 temperature sensor of 1000
Ω
at 0
°
C. Specifications according to DIN43760
•
Pt1000 temperature sensor of 1000
Ω
at 0
°
C. Specifications according to IEC 60751
3 x Analog Outputs supplying 0-10 VDC.
NB!
Please note the values available within the different standard groups of resistors:
E12: Closest standard value is 470
Ω
, creating an input of 449.9
Ω
and 8.997V.
E24: Closest standard value is 510
Ω
, creating an input of 486.4
Ω
and 9.728V.
E48: Closest standard value is 511
Ω
, creating an input of 487.3
Ω
and 9.746V.
E96: Closest standard value is 523
Ω
, creating an input of 498.2
Ω
and 9.964V.
Analog inputs - terminal X42/1-6
Parameter group for read out: 18-3*. See also
Programming Guide.
Parameter groups for set-up: 26-0*, 26-1*, 26-2* and 26-3*. See also
Programming Guide.
VLT
®
AQUA Drive Design Guide
3 VLT AQUA Selection
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
73
3
Содержание VLT AQUA Drive Series
Страница 38: ...3 VLT AQUA Selection VLT AQUA Drive Design Guide 38 MG 20 N5 02 VLT is a registered Danfoss trademark 3...
Страница 106: ...5 How to Install VLT AQUA Drive Design Guide 106 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 150: ...5 How to Install VLT AQUA Drive Design Guide 150 MG 20 N5 02 VLT is a registered Danfoss trademark 5...
Страница 168: ...7 RS 485 Installation and Set up VLT AQUA Drive Design Guide 168 MG 20 N5 02 VLT is a registered Danfoss trademark 7...
Страница 194: ...8 Troubleshooting VLT AQUA Drive Design Guide 194 MG 20 N5 02 VLT is a registered Danfoss trademark 8...