background image

   VLT

® 

6000 HVAC

15

MG.60.G2.02 - VLT is a registered Danfoss Trademark

6 4

6 4

6 4

6 4

6 4

PI I TIME

PI I TIME

PI I TIME

PI I TIME

PI I TIME (parameter 424) - This sets the

integral time for the VLT 6000 PID controller.

It can have a value between 0.01 seconds

and 9999 (OFF). In order for the controller to

function properly, this should not be rned off.

6 5

6 5

6 5

6 5

6 5

PI GAIN LIMIT

PI GAIN LIMIT

PI GAIN LIMIT

PI GAIN LIMIT

PI GAIN LIMIT (parameter 426) - This sets

the maximum derivative gain for the

VLT 6000 PID controller. It can have a value

between 5 and 50.

6 6

6 6

6 6

6 6

6 6

LOWP

LOWP

LOWP

LOWP

LOWPASS FL

ASS FL

ASS FL

ASS FL

ASS FLTR

TR

TR

TR

TR (parameter 427) - This sets

the time constant for the noise filter in the

VLT 6000 PID controller feedback loop. It

can have values between 0.01 and 10

seconds.

6 8

6 8

6 8

6 8

6 8

FB FUNCTION

FB FUNCTION

FB FUNCTION

FB FUNCTION

FB FUNCTION (parameter 417) - This sets

how the VLT 6000 PID controller responds to

the drive’s two feedback signals. Its value is

an integer between 0 and 6. Refer to the

V

LT 6000 Operating Instructions

 for the list of

choices and an explanation of each.

Network Outputs fr

Network Outputs fr

Network Outputs fr

Network Outputs fr

Network Outputs from the VL

om the VL

om the VL

om the VL

om the VLT 6000: 

T 6000: 

T 6000: 

T 6000: 

T 6000:  The  points

listed in Strategy One are commonly used.

 Network Connection

Table 3  Tightening Torque and Wire Gage

Analog Input Monitoring:

Points 87, 88 and 89 can be used to monitor the

value of the analog control signals applied to

terminals 53, 54 and 60. These points are active

even when NO FUNCTION is programmed for the

analog input of the drive. As a result, it is possible to

use the VLT 6000 analog inputs as analog input for

the FLN.

Drive Relay Control:

While relay 1 and 2 in the VLT 6000 usually provide

drive status indications, these indications are

generally not needed when the drive is connected to

an FLN. In some applications, it can be useful to

have the FLN control these relays. For example, by

controlling one of the relays, the FLN could select

the active pump in a pump sequencing system. For

the FLN to control a drive relay, the appropriate

VLT 6000 parameter (323 or 326) must be set to

CONTROL WORD 11/12. Setting point 40 or 41 to

ON will then activate the corresponding relay.

 

 ■

 ■

 ■

 ■

 ■

 VLT

 

6000 Special Functions

Safety Interlock:

The VLT 6000 can accept a safety interlock stop

command that is hard-wired to the drive control

terminals and another from the FLN. When

VLT 6000 parameter 304,

Digital Inputs

, is set to

SAFETY INTERLOCK, an open hard-wired safety

interlock will cause the drive to display ALARM 60

EXTERNAL FAULT.  Setting point 28 to COAST will

display UN. READY in the lower right corner of the

drive’s  display. The individual  displays for each

allow the operator to determine which device

caused the trip. VLT 6000 parameter 503, 

Coasting

Stop

, determines the interaction of these two

safety interlocks. See the 

VLT 6000 Operating

Instructions

 for details.

Connect the VLT 6000 to the FLN in accordance

with the following procedure (see Figure 2).

1.

Connect signal wires to terminal 68 (P+) and

terminal 69 (N-) on main control board of drive.

(See tightening torque and wire size in Table 3.)

2.

If shielded cabling is used, connect one end of

shield to terminal 61. This terminal is connected

to ground via an internal RC link.

NOTE:

NOTE:

NOTE:

NOTE:

NOTE:

It is recommended to use shielded, twisted-

pair cables to reduce noise between

conductors.

In addition to the control strategies described

above, the VLT 6000 provides additional control

flexibility to allow it to integrate into special control

systemrequirements. The following are just a few

examples.

Torque Specs 
 
 

4.5 in Ib/0.5 Nm 

Control wire 
 
 

18 24 

AWG, 

shielded, 

twisted pair/1.5 mm, 
shielded twisted pair 

 

Содержание VLT 6000 series

Страница 1: ...Parameter Data 7 Extended Menu 8 HP kW 8 VLT 6000 Functional Features Drive Operation 8 Motor and Drive Thermal Protection 8 Set up 1 4 8 Current Monitoring and Limits 9 Direction of Rotation 9 Start...

Страница 2: ...g Input Monitoring 15 Drive Relay Control 15 Network Connection Hardware Setup 16 Electrical Control Terminals 17 Typical Control Connection Examples 18 VLT 6000 Functional Features Startup of FLN Man...

Страница 3: ...Guidelines 1 The drive must be disconnected from the AC line before any service work is done 2 The Stop Off key on the local control panel of the drive does not disconnect the equip ment from the AC l...

Страница 4: ...t has been disconnected from AC line To be sure that capacitors have fully discharged wait 14 minutes for 220 and 500 V units and 30 minutes for 550 600 V units after power has been removed before tou...

Страница 5: ...is a Siemens registered trademark VLT is a Danfoss registered trademark The VLT 6000 frequency converter is delivered for installation and setup with the required applica tion parameters already progr...

Страница 6: ...will start and ramp up to this frequency when HAND START key is pressed If drive is already running in Auto Mode when HAND START is pressed drive will begin running in Hand Mode and in local control...

Страница 7: ...Press key once to change hundreds digit to 1 6 Press u key once to move cursor to tens digit Quick Menu Item Number Parameter Name Description 1 001 Language Selects language used for all displays 2 1...

Страница 8: ...are the system status what the motor and drive are doing and if there are any problems The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for advers...

Страница 9: ...incapable of stopping the drive The serial interface continues to access drive settings Hand Auto Modes 34 The SEL HND AUTO shows which mode the drive is in The drive can be commanded into either Han...

Страница 10: ...ENS SIEMENS SIEMENS SIEMENS DANFOSS DANFOSS DANFOSS DANFOSS GAIN GAIN GAIN GAIN I II I GAIN GAIN GAIN GAIN P P P P TIME TIME TIME TIME PI PI PI PI 667 667 667 667 GAIN GAIN GAIN GAIN P P P P GAIN GAIN...

Страница 11: ...oller This can be turned on or off depending on the requirements of the control strategy A brief summary of possibilities follows This is meant to illustrate possibilities rather than be all inclusive...

Страница 12: ...the drive will shut off immediately and the motor will coast to a stop When set to COAST the lower right corner of the drive display shows UN READY unit ready The drive will not start in either HAND...

Страница 13: ...ls from the FLN The FLN receives the feedback signal from the controlled system It sends this and the desired setpoint to the VLT 6000 PID controller The drive compares the feedback signal with the se...

Страница 14: ...oint 51 or parameter 205 If an attempt is made to set point 69 to a value outside of this range the setpoint will not be changed SETPOINT 1 can also be programmed using parameter 418 Setpoint 1 7 0 7...

Страница 15: ...in the VLT 6000 usually provide drive status indications these indications are generally not needed when the drive is connected to an FLN In some applications it can be useful to have the FLN control...

Страница 16: ...ply from the common of the digital inputs Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs When OFF the negative of an external power supply is conn...

Страница 17: ...t is 200 mA 16 33 Digital inputs R 2 kohm 5 V logical 0 10 V logical 1 16 33 30 VAC 42 5 VDC 1 A relay output can be used for indicating status and warnings 20 Voltage supply to digital inputs and ext...

Страница 18: ...ur Figur Figur Figure 6 e 6 e 6 e 6 e 6 Two Feedback Signals Connection T T T T Transmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection The drive...

Страница 19: ...e Interval and 566 FLN Time Interval Function can be commanded by the data points 36 and 37 see Table 9 NOTE NOTE NOTE NOTE NOTE Drive can store preset references programmed in parameters 211 through...

Страница 20: ...T 6000 LCP keypad Drive operation can then be controlled through the host network device in accordance with its operation instructions NOTE NOTE NOTE NOTE NOTE Default setting for point number 35 Run...

Страница 21: ...tage low X 7 Over voltage X X 8 Under voltage X X 9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16...

Страница 22: ...eadout Points 03 FREQ OUTPUT 0 HZ 0 1 0 16383 R 512 LAI 06 CURRENT 0 A 0 1 0 16383 R 514 LAI 08 POWER 0 KW 1 0 511 R 515 LAI 10 KWH 0 KWH 3 1 0 32767 R 602 LAI 12 RUN TIME 0 HRS 4 0 0 32767 R 601 LAI...

Страница 23: ...R 204 LAI 49 REF MAX S Note 4 UNIT 0 1 1638 3 32767 R 205 LAI Setpoint Related Points 50 REF MIN Note 3 0 UNIT 0 1 1638 3 32767 W 204 LAO 51 REF MAX Note 3 Note 4 UNIT 0 1 1638 3 32767 W 205 LAO 52 RE...

Страница 24: ...NOTENA ENABLE NOTENA R 527 2 LDI 81 DRV RDY STAT NOTRDY READY NOTRDY R 527 1 LDI 82 DRVCTRL STAT NOTRDY READY NOTRDY R 527 0 LDI 84 RESET NO RESET NO R 530 7 LDI 85 START OFF ON OFF R 530 6 LDI 86 Q...

Страница 25: ...n vary depending on settings of other points or the drive size Consult the VLT 6000 Operating Instructions for values Twelve special read only points can be used for checking if the value actually cha...

Страница 26: ...s been given a coast to stop command 28 CMD COAST Commands drive to make motor coast to a stop 29 DAY NIGHT Selects day or night mode Has no effect on drive operation 30 CURRENT LIM Sets maximum drive...

Страница 27: ...er 415 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent 75 AUTO RAMP Displays when drive deceleration rate is extende...

Отзывы: