MG.60.G2.02 - VLT is a registered Danfoss Trademark

Point Mapping Table

The VLT 6000 parameters, along with the internal

variables and readouts for controlling the drive via

the FLN serial bus, are organized as a Point Map.

Not all parameters and readouts are supported by

the FLN protocol. FLN points 01, 02, 20, 29 and 99

are predefined. Available points and a description of

their characteristics are listed in Table 8. Parameters

which can be written to (“W” in the Read/Write

column) are programmable through the FLN device,

others (“R”) are read-only, or read and write (“R/W”).

T

T

T

T

Table 8

able 8

able 8

able 8

able 8  Point Mapping

Point 

Number 

Descriptor 

Factory 

Default 

(SI Units) 

SI Units 

Slope 

(SI Units) 

Intercept 
(SI Units) 

Range 

On Text 

 

Off Text 

Read/ 

Write 

Param. 

number 

 

Network 

Port 

Type  

Note 1 

01 CTLR 

ADDRESS  1 

-- 

 

255 

-- 

-- 

R  501  Pre-

defined 

02 APPLICATION 2709  -- 

 

  255  -- 

--  R  --  Pre-

defined 

Readout Points 

{03} FREQ 

OUTPUT  0 

HZ 

0.1 

16383  -- 

-- 

R  512  LAI 

{06} CURRENT  0 

0.1 

0 16383 -- 

--  R 

514 LAI 

{08} POWER  0  KW  1 

0 511 --  -- R 

515 

LAI 

{10} KWH  0 

KWH 

3.1  0 

32767 

-- -- 

602 

LAI 

{12} RUN 

TIME  0  HRS  4.0 

0 32767 -- 

--  R 

601 

LAI 

{13} DC 

BUS 

VOLT  0  VOLTS 

1023  -- 

-- 

R  518  LAI 

{14} OUTPUT 

VOLT  0  VOLTS 

1023 

-- 

-- 

R  517  LAI 

{15} MOTOR 

THERM  0 

PCT 

255 

-- 

-- 

R  519  LAI 

{16} DRIVE 

THERM  0 

PCT 

255 

-- 

-- 

R  520  LAI 

{17} CURR. 

SETU   0 

-- 

255 

-- 

-- 

R  -- 

LAI 

{18} 

TIMERS 

STAT  0 

-- 

-- 

-- 

-- LIMIT OK R 

527-15 

LDI 

{19} 

CURRENT 

STAT 0 

-- 

-- 

-- 

-- LIMIT OK R 

527-14 

LDI 

20 OVRD 

TIME  1  HRS  1 

0  255  -- 

-- W -- Pre-

defined 

Status and Command Points 

{21} FWD.REV FWD  -- 

-- 

--  -- REV 

FWD 

532-8 

LDI 

{22} CMD 

FWD.REV FWD 

-- 

-- 

-- 

-- 

REV  FWD  W 

Cmd-15 

LDO 

{23} STOP.RUN 

STOP -- 

-- 

-- 

-- RUN 

STOP 

527-11 

LDI 

{24} CMD 

STP.STRT STOP 

-- 

-- 

-- 

--  START STOP  W Cmd-4 LDO 

{25} FREEZE 

OUT  NO 

-- 

-- 

-- 

-- FREEZE NO  R 

532-16 LDI 

{26} CMD 

FREEZE 

FREEZE  -- 

-- 

-- 

-- 

NO FREEZE 

Cmd-5 

LDO 

{27} COAST 

COAST 

--  -- 

--  -- NO 

COAST 

530-3 

LDI 

{28} CMD 

COAST 

COAST  -- 

-- 

-- 

--  NO COAST 

Cmd-3 

LDO 

Common Configuration Points 

29 DAY.NIGHT 

Note 2 

DAY -- 

-- 

-- 255 

NIGHT 

 

DAY 

-- 

Pre-

defined 

{30} CURRENT 

LIM 

Note 3 

Note 4 

0.1 

0.1 

16383 

-- 

-- 

215 

LAO 

{31} ACCEL 

TIME 

1 Note 

4  SEC 

4095 

-- 

--  R/W 206  LAO 

{32} DECEL 

TIME 

1 Note 

4  SEC 

4095 

-- 

--  R/W 207  LAO 

 

Содержание VLT 6000 series

Страница 1: ...Parameter Data 7 Extended Menu 8 HP kW 8 VLT 6000 Functional Features Drive Operation 8 Motor and Drive Thermal Protection 8 Set up 1 4 8 Current Monitoring and Limits 9 Direction of Rotation 9 Start...

Страница 2: ...g Input Monitoring 15 Drive Relay Control 15 Network Connection Hardware Setup 16 Electrical Control Terminals 17 Typical Control Connection Examples 18 VLT 6000 Functional Features Startup of FLN Man...

Страница 3: ...Guidelines 1 The drive must be disconnected from the AC line before any service work is done 2 The Stop Off key on the local control panel of the drive does not disconnect the equip ment from the AC l...

Страница 4: ...t has been disconnected from AC line To be sure that capacitors have fully discharged wait 14 minutes for 220 and 500 V units and 30 minutes for 550 600 V units after power has been removed before tou...

Страница 5: ...is a Siemens registered trademark VLT is a Danfoss registered trademark The VLT 6000 frequency converter is delivered for installation and setup with the required applica tion parameters already progr...

Страница 6: ...will start and ramp up to this frequency when HAND START key is pressed If drive is already running in Auto Mode when HAND START is pressed drive will begin running in Hand Mode and in local control...

Страница 7: ...Press key once to change hundreds digit to 1 6 Press u key once to move cursor to tens digit Quick Menu Item Number Parameter Name Description 1 001 Language Selects language used for all displays 2 1...

Страница 8: ...are the system status what the motor and drive are doing and if there are any problems The VLT 6000 continuously monitors all aspects of motor and drive status and issues alarms or warnings for advers...

Страница 9: ...incapable of stopping the drive The serial interface continues to access drive settings Hand Auto Modes 34 The SEL HND AUTO shows which mode the drive is in The drive can be commanded into either Han...

Страница 10: ...ENS SIEMENS SIEMENS SIEMENS DANFOSS DANFOSS DANFOSS DANFOSS GAIN GAIN GAIN GAIN I II I GAIN GAIN GAIN GAIN P P P P TIME TIME TIME TIME PI PI PI PI 667 667 667 667 GAIN GAIN GAIN GAIN P P P P GAIN GAIN...

Страница 11: ...oller This can be turned on or off depending on the requirements of the control strategy A brief summary of possibilities follows This is meant to illustrate possibilities rather than be all inclusive...

Страница 12: ...the drive will shut off immediately and the motor will coast to a stop When set to COAST the lower right corner of the drive display shows UN READY unit ready The drive will not start in either HAND...

Страница 13: ...ls from the FLN The FLN receives the feedback signal from the controlled system It sends this and the desired setpoint to the VLT 6000 PID controller The drive compares the feedback signal with the se...

Страница 14: ...oint 51 or parameter 205 If an attempt is made to set point 69 to a value outside of this range the setpoint will not be changed SETPOINT 1 can also be programmed using parameter 418 Setpoint 1 7 0 7...

Страница 15: ...in the VLT 6000 usually provide drive status indications these indications are generally not needed when the drive is connected to an FLN In some applications it can be useful to have the FLN control...

Страница 16: ...ply from the common of the digital inputs Normally this switch is ON and the power supply is present at terminals 12 and 13 for digital inputs When OFF the negative of an external power supply is conn...

Страница 17: ...t is 200 mA 16 33 Digital inputs R 2 kohm 5 V logical 0 10 V logical 1 16 33 30 VAC 42 5 VDC 1 A relay output can be used for indicating status and warnings 20 Voltage supply to digital inputs and ext...

Страница 18: ...ur Figur Figur Figure 6 e 6 e 6 e 6 e 6 Two Feedback Signals Connection T T T T Transmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection ransmitter Connection The drive...

Страница 19: ...e Interval and 566 FLN Time Interval Function can be commanded by the data points 36 and 37 see Table 9 NOTE NOTE NOTE NOTE NOTE Drive can store preset references programmed in parameters 211 through...

Страница 20: ...T 6000 LCP keypad Drive operation can then be controlled through the host network device in accordance with its operation instructions NOTE NOTE NOTE NOTE NOTE Default setting for point number 35 Run...

Страница 21: ...tage low X 7 Over voltage X X 8 Under voltage X X 9 Inverter time X X 10 Motor time X X 11 Motor thermistor X X 12 Current limit X X 13 Over current X X 14 Ground fault X X 15 Switch mode fault X X 16...

Страница 22: ...eadout Points 03 FREQ OUTPUT 0 HZ 0 1 0 16383 R 512 LAI 06 CURRENT 0 A 0 1 0 16383 R 514 LAI 08 POWER 0 KW 1 0 511 R 515 LAI 10 KWH 0 KWH 3 1 0 32767 R 602 LAI 12 RUN TIME 0 HRS 4 0 0 32767 R 601 LAI...

Страница 23: ...R 204 LAI 49 REF MAX S Note 4 UNIT 0 1 1638 3 32767 R 205 LAI Setpoint Related Points 50 REF MIN Note 3 0 UNIT 0 1 1638 3 32767 W 204 LAO 51 REF MAX Note 3 Note 4 UNIT 0 1 1638 3 32767 W 205 LAO 52 RE...

Страница 24: ...NOTENA ENABLE NOTENA R 527 2 LDI 81 DRV RDY STAT NOTRDY READY NOTRDY R 527 1 LDI 82 DRVCTRL STAT NOTRDY READY NOTRDY R 527 0 LDI 84 RESET NO RESET NO R 530 7 LDI 85 START OFF ON OFF R 530 6 LDI 86 Q...

Страница 25: ...n vary depending on settings of other points or the drive size Consult the VLT 6000 Operating Instructions for values Twelve special read only points can be used for checking if the value actually cha...

Страница 26: ...s been given a coast to stop command 28 CMD COAST Commands drive to make motor coast to a stop 29 DAY NIGHT Selects day or night mode Has no effect on drive operation 30 CURRENT LIM Sets maximum drive...

Страница 27: ...er 415 73 BUS FB 1 Supplies feedback value for bus feedback 1 in percent 74 BUS FB 2 Supplies feedback value for bus feedback 2 in percent 75 AUTO RAMP Displays when drive deceleration rate is extende...

Отзывы: