29
★
= ROM default setting. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
VLT
®
Series 2000
Programming
408 Terminal 46 Output (TERMINAL 46 OUTPUT)
Value:
Unit Ready (UNIT READY)
[0]
★
Unit Ready Remote Control (UNT RDY RCTL)
[1]
Enabled not Warning (ENABLED no WR)
[2]
Running (RUNNING)
[3]
Running, no warning (RUNNING noWR)
[4]
Running in range, no warning (RUNinRANGE)
[5]
Speed = reference, no warning (RUN@REF noWR) [6]
Alarm (ALARM)
[7]
Alarm or warning (ALARM or WARN)
[8]
Current limit (CURRENT LIMIT)
[9]
Out of frequency range (OUT FREQ RGE)
[10]
Out of current range (OUT CURR RGE)
[11]
Reversing (REVERSING)
[12]
Pulse output 15 Hz - 1.5 kHz (PULSEOUT 1500)
[13]
Pulse output 15 Hz - 3.0 kHz (PULSEOUT 3000)
[14]
Pulse output 15 Hz - value par. 005 (PULSPAR005) [15]
Send/receive RS485 (CTS/RTS-RS485)
[18]
Receive/send RS485 (CTS/RTS-RS485)
[19]
Function:
Using this parameter you can choose between different
output signals. The output is an open collector output and
therefore a pull-up resistor must be connected to terminal
12 (+24 V).
Description:
For the pulse output the lowest output frequency is 15 Hz
and the highest output frequency is 5 Hz.
RS 485 send/receive control is used when the serial port is
connected to the RS 485 network via a RS 232/RS 485
adapter.
VLT
12
46
20
VLT
12
46
20
VLT
12
20
Connection example where the signal is active high:
Connection example where the signal is active low:
Connection example using RS 232/485 adapter:
12V
SND/RCV
I
max
= 40mA
Imp
min
= 600
Imp
min
= 600
I
max
= 30mA
I
max
= 40mA
Imp
min
= 600
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com