VLT
®
Series 2000
10
Quick Setup
If you know how to operate the VLT Series and and are
familiar with the menus and parameters, go directly to the
How to Program section of this manual.
How to Program
This setup is based on the assumption that you want
your VLT to operate with the following:
1. External start/stop
2. Potentiometer connected for external speed control
3. Option to change rotation direction
4. Option to select a fixed speed (Jog)
If you are not familiar with the VLT Series Adjustable
Frequency Drive refer first the Operation section of this
manual.
NOTE: If you use a brake module, you must program
parameter 300. If you want local operation via the display
keys you must program parameters 003 and 004. To
store the data press the "Menu" key.
If you have connected your VLT as shown in the Typical
Wiring Example, you must program the parameters as
listed in the chart below.
Standard motor with constant torque load without a brake module on the adjustable frequenct drive
Step
Parameter
Designation
Settings
Display Indication
1
000
Language
Choose
English
ENGLISH
2
103
Motor output
Read motor plate
3
104
Motor voltage
Read motor plate
4
105
Motor frequency
Read motor plate
5
201
Minimum frequency
Set wanted frequency
6
202
Maximum frequency
Set wanted frequency
7
215
Ramp up 1
Set wanted ramping time
8
216
Ramp down 1
Set wanted ramping time
9
Start the
This is done by supplying terminals 18 and 27 with 24 VDC from
adjustable frequency
the adjustable frequency drive's terminal 12 or by using an
drive
external 24 VDC voltage.
If a brake module is mounted, program the following parameters
Step
Parameter
Designation
Settings
Display Indication
1
300
Brake function
If a brake module is used, choose
Applied
APPLIED
2
Start the
This is done by supplying terminals 18 and 27 with 24 VDC from
adjustable frequency
the adjustable frequency drive's terminal 12 or by using an
drive
external 24 VDC voltage.
If you want local operation and start, program the following parameters
Step
Parameter
Designation
Settings
Display Indication
1
003
Operation site
Choose
Loc/ext stop
LOC/EXT STOP
2
004
Local reference
Record wanted output frequency by means of the "+" and "–" keys
Installation; Quick Setup