Electrical installation (continued)
Item 2
Extra protection
If you want extra protection, pay attention to the
following:
As extra protection, error voltage relays or neutral
grounding can be used. However, the installation
must comply with local health and safety standards.
An earth fault can introduce a direct current in the
discharge current. Any ELCB relay used must comply
with local regulations. The relays must be suitable to
protect three-phase equipment with bridge rectifier
and short discharge on power-up.
Item 3
Motor, mains and brake cables
To comply with the stated EMC emission
specifications, screened motor cable must not be
used. However, a precondition is that an RFI filter
module is installed to comply with the EMC emission
specifications.
Observe the following max. cross sections for motor,
mains and brake cables:
■
That I have done
Mains supply 1 x 220/230/240 V
3 x 208/220/230/240 V
VLT 2010
Max. 4 mm
2
VLT 2015
Max. 4 mm
2
VLT 2020
Max. 4 mm
2
VLT 2030
Max. 4 mm
2
VLT 2040
Max. 4 mm
2
VLT 2050
Max. 4 mm
2
Installation
▲▲▲▲▲
Cable relief fitting
195H6129
Option
Mains supply 3 x 380-460 V
VLT 2020
Max. 4 mm
2
VLT 2025
Max. 4 mm
2
VLT 2030
Max. 4 mm
2
VLT 2040
Max. 4 mm
2
VLT 2050
Max. 4 mm
2
VLT 2060
Max. 4 mm
2