![Danfoss VLT 2000 Series Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/danfoss/vlt-2000-series/vlt-2000-series_manual_3438450031.webp)
MG.20.B6.02 – VLT is a registered Danfoss trademark
31
VLT
®
2000 Series
Section 1
Section 2
Section 3
Which one to choose?
Mains: 1
×
220/230/240 V, 3
×
208/220/230/240 V
VLT type
Typical shaft output
Constant output current I
VLT,N
Constant output power at 230 V
[kW]
[A]
[kVA]
2010
0.37
2.2
0.9
2015
0.55
3.1
1.3
2020
0.75
4.0
1.6
2030
1.5
7.5
3.1
2040 *)
2.2
10.6
4.4
2050 *)
3.0
16.7
6.9
*) VLT types 2040 and 2050: only three-phase mains supply.
Mains: 3
×
380/400/415/440/460 V *)
VLT type
Typical shaft output
Constant output current I
VLT,N
Constant output power at 415 V
[kW]
[A]
[kVA]
2020
0.75
2.4
1.7
2025
1.1
2.8
2.0
2030
1.5
4.0
2.9
2040
2.2
5.6
4.0
2050
3.0
7.6
5.5
2060 *)
4.0
9.7
7.0
*) VLT type 2060: 3
×
380/400/415 V
How to size your VL
T
■