MG.20.B6.02 – VLT is a registered Danfoss trademark
VLT
®
2000 Series
38
How to size your VL
T
Technical data
Mains: 1
×××××
220/230/240 V, 3
×××××
208/220/230/240 V
3 x 208/220/230/240 V
Meets the international standards, UL/ cUL
4
)
VLT type
2010
2015
2020
2030
2040
2050
Constant load (CT):
Output current
I
VLT.N
[A]
2.2
3.1
4.0
7.5
10.6
16.7
I
VLT.MAX
[A] (60 s)
3.5
4.9
6.3
10.5
17.0
26.7
Output
S
VLT.N
[kVA]
0.9
1.3
1.6
3.1
4.4
6.9
S
VLT.MAX
[kVA] (60 s)
1.4
2.1
2.6
4.3
7.0
11.0
Typical shaft output
P
VLT.N
[kW]
0.37
0.55
0.75
1.5
2.2
3.0
Max. cable cross section
[mm
2
]
4
4
4
4
4
4
Max. motor cable length
[m]
40 (with motor coils IP 10:
unscreened cables 300 m, screened cables 150 m)
Output voltage
U
M
[%]
0-100% of mains voltage
Output frequency
f
M
[Hz]
0-120 or 0-500; programmable
Rated motor voltage
U
M,N
[V]
200/208/220/230/240
Rated motor frequency
f
M,N
[Hz]
50/60/87/100
Thermal motor protection during operation
Built-in thermal motor protection (electronic)
Switching on the output
Unlimited (frequent switching may cause cut-out)
Ramp times
[s]
0.1-800
VLT type
2010
2015
2020
2030
2040
2050
Max. input current
I
L,N
[A]
(5.3/3.5) (8.5/5.6)
(10.6/7.1)
(18/12)
(-/10)
(-/16)
Max. cable cross section
[mm
2
]
4
4
4
4
4
4
Max. prefuses
[A]
10
16
20
20
20
25
Bussmann Fuse type KTN-R 250 V AC
5
)
[A]
10
15
20
20
20
25
Mains supply voltage
[V]
1 x 220/230/240 ±10 %
3 x 208/220/
3
×
208/220/230/240 ±10 %
230/240±10 %
Mains supply frequency
[Hz]
50/60
Power factor/cos.
ϕ
1
Without mains filter:0.50/0.87
0.90/1.0
0.90/1.0
With mains filter:0.65/1.0
Efficiency
>0.94 at rated load
Switching on the input
times/min.
5
VLT type
2010
2015
2020
2030
2040
2050
Weight [kg]
IP 20
2.0
2.0
2.1
2.1
4.6
4.6
Weight [kg] with built-in RFI filter
IP 20
3.7
3.7
3.8
3.8
Power loss at max. load
CT [W]
39
53
69
126
136
236
Enclosure
IP 20
IP 20
IP 20
IP 20
IP 20
IP 20
Vibration test
[g]
0.7
Relative humidity
[%]
Max. 95 IEC 721 (according to VDE 0160)
Ambient temperature
[
°
C]
0
→
+40 at full-load operation
2
)
(according to VDE 0160)
[
°
C]
−
25
→
+70, storage/transport
Frequency converter protection
Grounding and short-circuit proof
3
)
EMC applied standards
Emission
EN 55011, Group 1, Class A,
(see page 90)
CISPR 11 (with RFI and motor filter)
Immunity
IEC 1000-4
UL file-number
E134261
2
)
In the range -10 - 0 °C the unit can start and run, but the display indications and certain operating characteristics
will not meet the specifications.
3
)
Brake option without protection
4
)
Units with built-in RFI filter are not UL-approved.
5
)
For the North American market
■