If,  when  the  compressor  attempts  to  start,  the  voltage  reading  drops 
significantly,  a  bad  electrical  connection  should  be  suspected.  If  the  voltage 
drop is sufficient to fall below the 10.5v (23v) cut-off built in to the controller, 
the  compressor  will  stop.  (At  this  point  the  voltage  may  return  to  it s  original 
reading.) The fan or pump will continue to run for approx. 45 seconds and then 
the  compressor  will  attempt  a  re-start.  If  the  voltage  is  then  above  11.5v 
(23.5v) the compressor will start or attempt to re-start again. 

 

WARNING

   If  the  multi-meter  being  used  is  a  digital  model  that  is  slow  to 

react, the voltage may drop below 10.5v (23v) and then recover too quickly to 
register  on  the  meter.  This  can  lead  to  the  situation  where  the  compressor 
starts then stops from low voltage, the voltage returns to its

 

original value, and 

there being no significant drop on the meter. 

 

If the compressor starts and runs OK but stops after a short while, the voltage 
may  be  gradually  dropping  towards  and  below  the  10.5v  (23v)  cut-off  point. 
This should be easily identified on the meter. 

 

If  the  nature  of  the  fault  is  such  that  the  voltage  reading  at  5  above  drops 
below  10.5v  (23v)  even  before  the  compressor  attempts  to  start,  a  very  bad 
electrical connection must be suspected. This is because even the small load of 
the  fan  or  pump  relay,  both  less  than  0.5  amp  (0.25  amp),  is  seemingly 
sufficient to reduce the voltage considerably.     

What to look for 
A loose and/or high-resistance connection can be anywhere in the supply between 
the  batteries  and  the  controller.  i.e.  a  bad  breaker  or  fuse,  a  loose  or  corroded 
screw connection, a poorly made or corroded crimp connection, a damaged section 
of wire, etc. 

 

HINT

  

A good place to look first is the negative (ground) connection, especially on a 
European-built  boat.  These  tend  to  be  multiple,  common  connections  that 
are added to over time. 

  

2  Flashes  Fan Greater 1 amp 

 

a.

 

Air cooled systems 

The fan is faulty and drawing more than 1 amp.  

Unplug the fan or water pump and restart the compressor.   
For air cooled you will need to replace the fan: 