4. Connect the cables. See the correct tightening torques in
12.6 Tightening Torques of the Terminals
.
•
Connect the phase conductors of the mains cable and of the motor cable into the correct terminals. If a brake resistor cable is
used, connect its conductors into the correct terminals.
•
Attach the grounding conductor of each cable to a grounding terminal with a grounding clamp for grounding conductor.
5. To make a 360° connection with the grounding clamp for cable shield, expose the shield of motor cables.
e3
0b
g1
04
.2
0
2
1
1 Grounding clamp
2 Exposed shield
6. Attach the grounding clamps for control cable on the grounding level with M4x16 screws. Use the clamps delivered in the
accessories bag. Use the clamps to ground the control cables. Connect the control cables.
Electrical Installation
Operating Guide | VACON® NXS/NXP Air-cooled
AQ275638903263en-000301 / DPD00910