e
3
0
b
g
0
3
9
.1
0
IH
IH*150%
1 min
9 min
IH*150%
I
t
Illustration 81: High Overload
For more information, refer to the standard IEC61800-2.
12.7.2 Power Ratings for Mains Voltage 208–240 V
Table 51: Power Ratings in Mains 208–240 V, 50 Hz, 3~
Enclo‐
sure
size
Drive
type
Input
current
I
in
(1)
Low load‐
ability: I
L
[A]
(2)
Low load‐
ability:
10%
overload
I [A]
High
loadabili‐
ty: I
H
[A]
(2)
High
loadabili‐
ty: 50%
overload
I [A]
Loadabili‐
ty: Max I
S
2 s
Motor
shaft
power
(3)
:
10% over‐
load 40°C
[kW]
Motor
shaft
power
(3)
:
50% over‐
load 50°C
[kW]
FR4
0003
3.7
3.7
4.1
2.4
3.6
4.8
0.55
0.37
0004
4.8
4.8
5.3
3.7
5.6
7.4
0.75
0.55
0007
6.6
6.6
7.3
4.8
7.2
9.6
1.1
0.75
0008
7.8
7.8
8.6
6.6
9.9
13.2
1.5
1.1
0011
11
11.0
12.1
7.8
11.7
15.6
2.2
1.5
0012
12.5
12.5
13.8
11.0
16.5
22.0
3.0
2.2
FR5
0017
17.5
17.5
19.3
12.5
18.8
25.0
4.0
3.0
0025
25
25
27.5
17.5
26.3
35.0
5.5
4.0
0031
31
31
34.1
25.0
37.5
50.0
7.5
5.5
FR6
0048
48
48
52.8
31.0
46.5
62.0
11.0
7.5
0061
61
61.0
67.1
48.0
72.0
96.0
15.0
11.0
FR7
0075
75
75.0
83.0
61.0
92.0
122.0
22.0
15.0
0088
88
88.0
97.0
75.0
113.0
150.0
22.0
22.0
0114
114
114.0
125.0
88.0
132.0
176.0
30.0
22.0
Specifications
Operating Guide | VACON® NXS/NXP Air-cooled
AQ275638903263en-000301 / DPD00910
182 | Danfoss A/S © 2020.02