Enclo-
sure
size
Drive Type
I
L
[A]
Fuse
(gG/g
L) [A]
Mains, motor, and brake resistor
(1)
cable Cu [mm
2
]
Mains terminal cable size
[mm
2
]
Grounding
terminal ca-
ble size
[mm
2
]
MR6
0007 7
7.5
10
3x2.5+2.5
2.5–50 Cu/Al
2.5–35
0010 7
10.0
16
3x2.5+2.5
2.5–50 Cu/Al
2.5–35
0013 7
13.5
16
3x6+6
2.5–50 Cu/Al
2.5–35
0018 6
0018 7
18.0
20
3x10+10
2.5–50 Cu/Al
2.5–35
0022 6
0022 7
22.0
25
3x10+10
2.5–50 Cu/Al
2.5–35
0027 6
0027 7
27.0
32
3x10+10
2.5–50 Cu/Al
2.5–35
0034 6
0034 7
34.0
35
3x16+16
2.5–50 Cu/Al
2.5–35
MR7
0041 6
0041 7
41.0
50
3x16+16 (Cu)
3x25+16 (Al)
6–70 Cu/Al
6–70
0052 6
0052 7
52.0
63
3x25+16 (Cu)
3x35+16 (Al)
6–70 Cu/Al
6–70
0062 6
0062 7
62.0
63
3x25+16 (Cu)
3x35+16 (Al)
6–70 Cu/Al
6–70
MR8
0080 6
0080 7
80.0
80
3x35+16 (Cu)
3x50+21 (Al)
Bolt size M8
Bolt size M8
0100 6
0100 7
100.0
100
3x50+25 (Cu)
3x70+21 (Al)
Bolt size M8
Bolt size M8
0125 6
0125 7
125.0
125
3x70+35 (Cu)
3x95+29 (Al)
Bolt size M8
Bolt size M8
MR9A
0144 6
0144 7
144.0
160
3x70+35 (Cu)
3x120+41 (Al)
Bolt size M10
Bolt size M8
0170 6
0170 7
170.0
200
3x95+50 (Cu)
3x150+41 (Al)
Bolt size M10
Bolt size M8
0208 6
0208 7
208.0
250
3x120+70 (Cu)
3x185+57 (Al)
Bolt size M10
Bolt size M8
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
108 | Danfoss A/S © 2019.05