En-
clo-
sure
size
Drive
type
(1)
Low
Loada-
bility:
Contin-
uous
current
I
L
[A]
(2)
Low
Loada-
bility:
Input
current
I
in
[A]
(2)
Low
Loada-
bility:
10%
over-
load
current
[A]
(2)
High
load-
abili-
ty:
Con-
tinu-
ous
cur-
rent
I
H
[A]
(2)
High
load-
abili-
ty: In-
put
cur-
rent
I
in
[A]
(2)
High
loada-
bility:
50%
over-
load
cur-
rent
[A]
(2)
Loada-
bility:
Max
cur-
rent I
s
2 s
(2)
Motor
shaft
power
(3)
:
10%
over-
load
40°C
[kW]
Motor
shaft
power
(3)
:
50%
over-
load
50°C
[kW]
Motor
shaft
power
(3)
: 10%
over-
load
40°C
[hp]
Mo-
tor
shaft
pow-
er
(3)
:
50%
over-
load
50°C
[hp]
MR6
0048
48.0
43.8
52.8
31.0
28.5
46.5
62.0
11.0
7.5
15.0
10.0
0062
62.0
57.0
68.2
48.0
44.2
72.0
96.0
15.0
11.0
20.0
15.0
MR7
0075
75.0
69.0
82.5
62.0
57.0
93.0
124.0
18.5
15.0
25.0
20.0
0088
88.0
82.1
96.8
75.0
70.0
112.5
150.0
22.0
18.5
30.0
25.0
0105
105.0
99.0
115.5
88.0
82.1
132.0
176.0
30.0
22.0
40.0
30.0
MR8
0140
140.0
135.1
154.0
114.0
109.0
171.0
210.0
37.0
30.0
50.0
40.0
0170
170.0
162.0
187.0
140.0
133.0
210.0
280.0
45.0
37.0
60.0
50.0
0205
205.0
200.0
225.5
170.0
163.0
255.0
340.0
55.0
45.0
75.0
60.0
MR9A
0261
261.0
253.0
287.1
211.0
210.0
316.5
410.0
75.0
55.0
100.0
75.0
0310
310.0
301.0
341.0
251.0
246.0
376.5
502.0
90.0
75.0
125.0
100.0
1
The currents in given ambient temperatures are achieved only when the switching frequency is the same or smaller than the factory default
2
See
.
3
230 V
If the process includes a cyclical load, for example if there are lifts or winches, speak to the manufacturer to get the dimensioning
information.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 115
Danfoss A/S © 2019.05