The grounding clamp for cable shield
C
The grounding terminal
E
The brake resistor cable
B
The terminals
D
The mains cable
F
The motor cable
Illustration 13: Connecting the Stripped Cables
9.
Make sure that the grounding conductor is connected to the motor and also to the terminals that are identified with the PE symbol.
A
To comply with the requirements of the standard EN 61800-5-1, obey the instructions in
.
B
If a double grounding is necessary, use the grounding terminal under the drive. Use an M5 screw and tighten it to 2.0 Nm or
17.7 lb-in.
e3
0b
h2
28
.1
0
= M5; 2 Nm
10.
Attach again the cable cover.
Electrical Installation
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 47