Monitor Program Data and Controls
40
Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
6.9.1 Compressor Controller Settings
Select the “CC_Control” tab to view the following:
• Monitor program measurement unit selected
• Compressor Control Mode
• Chiller Control Parameters
• Compressor Startup Parameters
The compressor controller parameters are described in
Table 15.
Figure 30 EEPROM Settings - Compressor Controller Settings
Table 15 EEPROM Settings - Compressor Controller Parameters
Parameter
Description
Control Mode
Displays the source of demand for the compressor: Calibration,
Manual Control, Analog Input, Modbus Network, or Chiller Control.
Refer to 6.3.1 "Compressor Control Modes" on page 26 for further
details.
Display Units
Displays the measurement unit used. The options are:
• Metric Units - kPa, ºC, ºK
• Imperial Units - Psi, ºF, ºR
Refer to 6.3.1 "Compressor Control Modes" for details on how to
change the measurement unit.
Chiller Control Parameters:
Refer to 6.7 "Chiller Control" on page 36 for further details.