Monitor Program Data and Controls
20
Danfoss Turbocor Compressors Inc.
ECD-00007M Rev. 1
6.2
Bearing Calibration
The “Calibration Data” window allows the user to view and
compare the data of the latest calibration performed with
the latest stored calibration data, thus allowing the user to
verify that the bearing calibration was performed
successfully. It also allows the user to perform a manual
bearing calibration.
To view the “Calibration Data” window: from the menu
bar, select “Advanced”
→
“Bearing Calibration” .
NOTE:
Bearing calibration is always automatically performed
during compressor startup.
The “Description” column lists the calibration data
parameters. A more detailed description of the calibration
data parameters is provided in Table 5.
The “Latest Check” column shows the calibration data of
the latest calibration performed.
The “Stored Calibration” column shows the calibration data
of the latest saved calibration data.
The “Diff” column shows the difference between the
“Latest Check” value and the “Stored Calibration” value.
Clicking on the “Save Calibration” button stores the data
from the “Latest Check” as the “Stored Calibration” data.
Clicking on the “Save Data To File” button saves the
calibration data displayed on the “Calibration Data” screen
to a .csv file, which may be viewed using a spreadsheet
editor such as Microsoft® Excel.
Clicking on the “Perform Calibration” button, performs a
manual bearing calibration.
Figure 20 Bearing Calibration Window
Table 5 Calibration Data Details
Data Parameter
Description
FRX Min
Minimum DC voltage indicating minimum front radial x displacement.
FRX Max
Maximum DC voltage indicating maximum front radial x displacement.
FRY Min
Minimum DC voltage indicating minimum front radial y displacement.