Electrical Specifications
All Turbocor compressors have been tested in accordance with IEC Standard 1000-4-4.
Electrical Fast Transient/Burst Requirement. For additional protection, a surge suppressor
can be installed in parallel with the compressor. It is recommended to install surge
suppression in sites that are susceptible to lighting.
If it is necessary to provide additional harmonic reduction beyond that provided by the
standard 5% line reactor, DTC recommends the installation of a harmonic filter device in
parallel with the compressor as shown in Figure 20-9.
6.8 Surge Protection
6.9 Harmonic Filtering
(IEEE 519)
1. All metal parts should be connected to ground, including the shields of electrical
cables.
2. Verify continuity of all ground connections.
3. Ensure solid ground connections (both mechanical and electrical). Connections must
be clean, and grease and paint free.
4. At one point, usually the entrance of the power supply panel, all grounds should be
connected together (refer to Section 6.11).
From an EMC standpoint, it is best to categorize different types of grounds and treat them
independently (see Figure 6-1):
• Safety ground (Protective Earth [PE]) and shields of mains cables.
• Analog grounds, shielding of interface cables.
• Digital grounds.
• Reference ground (panel doors, backplate, etc.).
6.10 Grounding (Earth)
Connection Guidelines
NOTE
All TT compressors are compliant with standards:
IEC 60335-2-34:2002
IEC 60335-1:2007
EN 61000-6-2:2005
EN 61000-6-4:2007
2004/95/EC
2006/42/EC
strands, is recommended for best grounding performance. The multiple-strand cabling
provides more surface area in order to conduct the high frequencies that are on the
grounding cable.
Radiation of noise is also a concern for power line routing as it can effectively bypass the
filter. Input and output filter leads should be separated by a maximum practical distance
within enclosures and should be routed separately in interconnecting conduits when used.
Содержание TG230 Series
Страница 2: ...Page 2 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 8: ...Page 8 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 18: ...Page 18 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 32: ...Page 32 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 36: ...Page 36 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 44: ...Page 44 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...Page 50 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 52: ...Page 52 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 54: ...Page 54 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 56: ...Page 56 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 58: ...Page 58 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 70: ...Page 70 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 74: ...Page 74 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 77: ...Page 77 of 108 M AP 001 EN Rev N Physical Data 16 2 Center of Gravity Figure 16 4a Center of Gravity ...
Страница 81: ...Page 81 of 108 M AP 001 EN Rev N Physical Data Figure 16 8 Discharge Port Detail TT700 and TG520 Gas Flow ...
Страница 82: ...Page 82 of 108 M AP 001 EN Rev N Physical Data Figure 16 9 Suction Port All Models ...
Страница 88: ...Page 88 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 90: ...Page 90 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 92: ...Page 92 of 108 M AP 001 EN Rev N THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...Page 104 of 108 M AP 001 EN Rev N Appendix A Power Line Accessories Installation Figure A 1 Line Reactor Connections ...