Termix VVX-I-R FI - 7 Series DS fully insulated

Troubleshooting

Area of operation

Problem

Possible cause

Solution

Instantaneous water heater, 
thermostatic    

Incorrect DHW 
temperature

The strainer in the supply 
or return line is clogged up

Clean the strainer

Too high DHW flow rate

Check the dimensioning of DHW load, actual flow 
temperature and differential pressure

Defective mixer tap

Check if the mixer tap is defective and if so, replace

Defective or blocked check 
valve on the circulation valve

Check and replace if defective

Incorrect set-point on the 
DHW controller

Set the DHW controller’s thermostat to the correct value 
according to the section “Adjustments, domestic hot water”

Defective DHW controller

1)  Check the sensor: Remove the sensor head from 

the valve. If the DHW temperature then increases, 
replace the sensor 

2)  If the DHW temperature does not increase, 

replace the entire valve

Plate heat exchanger has calcified Replace the heat exchanger

Domestic hot water 
flow is too low

The filter on the cold water supply 
is clogged up

Clean the filter

Plate heat exchanger has calcified Replace the heat exchanger

Long wait for 
domestic hot water

Idle temperature is too low

Set the DHW controller’s thermostat to the correct value 
according to the section “Adjustments, domestic hot water”

DHW circulation temperature 
has been set too low

Set the thermostat higher or turn up the DHW circulation 
pump

Indirect heating, thermostatic

Incorrect flow 
temperature for 
space heating

The strainer in the supply 
or return line is clogged up

Clean the strainer

Incorrect set-point on the 
temperature controller

Set the thermostat of the temperature controller to 
the correct value according to the section “Temperature 
control of heating unit”

Defective temperature controller

1)  Check the controller: Remove the thermostat 

from the valve. If the temperature then increases, 
replace the thermostat 

2)  Alternatively, check and exercise the valve. 

Replace the valve if defective

Incorrectly set differential 
pressure regulator

Set the differential pressure regulator to the correct value 
according to the section “Differential pressure regulator”

Defective differential pressure 
regulator

Check and replace if defective

Air bubbles in the system

Bleed the installation thoroughly

Incorrect system pressure

Check the system pressure on a pressure gauge 
and top up with water if necessary

The pump is not working

Check whether there is power to the pump

Air in the pump

Make sure there is no air in the pump housing 

The pump is blocked

Exercise the pump using the centre screw

The pump has been set at too 
low a level

Set the pump correctly, see the section 
“Circulation pump UPM3”

Uneven heat distribution in the 
building due to incorrectly set 
balancing valves on heat emitters

Adjust or install balancing valves

Blocked heat exchanger

Flush the system and check that a strainer has been fitted 
on the secondary side. Then replace the heat exchanger

Primary return 
temperature 
too high

Space heating flow temperature 
is too high

Set the thermostat of the temperature controller to the 
correct value according to the section “Temperature control 
of heating unit”

Defective temperature controller

1)  Check the controller: Remove the thermostat 

from the valve. If the temperature then increases, 
replace the thermostat

2)  Alternatively, check and exercise the valve. 

Replace the valve if defective

Incorrect setting or dimensioning 
of the building’s heat emitters

Check, set, replace

Pump pressure is too high

Set the pump to a lower setting, see the section 
“Circulation pump UPM3”

Defective non-return valve

Check and replace if defective

Blocked heat exchanger

Flush the system and check that a strainer has been fitted 
on the secondary side. Then replace the heat exchanger

Noise in the unit

Incorrectly set differential 
pressure regulator

Set the differential pressure regulator to the correct value 
according to the section “Differential pressure regulator”

Defective differential 
pressure regulator

Check and replace if defective

Pump pressure is too high

Set the pump to a lower setting, see the section 
“Circulation pump UPM3”

Содержание Termix VVX-I-R FI - 7 Series

Страница 1: ...Danfoss 2021 06 LGB40450 Termix VVX I R FI 7 Series DS fully insulated Operating Guide...

Страница 2: ...12 Schematic description Termix VVX I R FI RAD 13 Schematic description Termix VVX I R FI UFH 14 Electrical connections and wiring 15 Wiring diagram radiator heating 16 Wiring diagram underfloor heat...

Страница 3: ...cian All electrical connections must be carried out by an authorised electrician Daily operations After correct installation and commissioning under normal circumstances further adjustment of the unit...

Страница 4: ...ow medium should not exceed 150 mg l The risk of corrosion increases significantly if the recommended chloride content is exceeded REACH All products from Gemina Termix A S meet the requirements in RE...

Страница 5: ...ries DS fully insulated Unit label The unit label is affixed to the back plate Image of a unit label is shown as an example Should the unit label become unreadable damaged or fall off completely then...

Страница 6: ...vel 55 dB Ambient temp 0 40 C in continuous use Dimensions for connections DHF DHR HFL HRL DCW DHW G internal thread Weight Net weight Approx 28 kg Dimensions Dimensions H 690 mm x W 530 mm x D 235 mm...

Страница 7: ...tions during transport and lifting handling it is important that all union connections are re tightened After filling the system with water and once it is in operation all union connections must be re...

Страница 8: ...he factory Assembly installation and commissioning Unpacking and preparation Remove the packaging from the unit Cling film and cardboard must be disposed of in accordance with locally applicable legis...

Страница 9: ...U shaped front Unhook and secure the front Lift the heat interface unit in the following two places 1 On the left hand side around the primary strainer 2 On the right hand side around the T piece bel...

Страница 10: ...10 Danfoss 2021 06 LGB40450 Termix VVX I R FI 7 Series DS fully insulated Dismantling the insulation front Temporary securing of centre plate Disassembly of the side frame...

Страница 11: ...act your supplier Tightening Due to vibrations during transit lifting and handling all heat interface unit connections must be checked and tightened before installation Strainer If a strainer is suppl...

Страница 12: ...sure Absorber with non return valve 2B Double check valve WRAS 31 Differential pressure controller 63 Sieve 4 Safety valve 38 Expansion tank 69 On off valve 7 Thermostatic controller HE 41B Fitting pi...

Страница 13: ...manual M Electrical wiring box 20 Filling drain valve 62B Pressure Absorber with non return valve 1 Isolation valve 26 Pressure gauge 63 Sieve 2B Double check valve WRAS 31 Differential pressure contr...

Страница 14: ...trical wiring box 24 Delivered loose with unit 62B Pressure Absorber with non return valve 1 Isolation valve 26 Pressure gauge 63 Sieve 2B Double check valve WRAS 31 Differential pressure controller 6...

Страница 15: ...nd IEC 60364 5 54 2011 The bonding point is located on the bottom of the mounting plate in the right corner and marked with an earth symbol Disconnection The electrically connected heat interface unit...

Страница 16: ...16 Danfoss 2021 06 LGB40450 Termix VVX I R FI 7 Series DS fully insulated Wiring diagram underfloor heating Wiring diagram radiator heating...

Страница 17: ...upply and DH Return if there is water in the system Loosen nuts Loosen the nuts on the fitting piece Remove fitting piece Remove the fitting piece and replace it with the energy meter Don t forget the...

Страница 18: ...osed the plug removed and a supply hose connected On re opening the isolation valve system fill can commence 4 Pre pressure The expansion vessel is supplied prepressurised to 0 5 bar The pre pressure...

Страница 19: ...ng of the secondary heating system Step 1 Remove the front and centre plate Step 2 Remove the cap and connect the flexible hose Step 3 Open both valves Step 4 After filling up the secondary heating sy...

Страница 20: ...t the pump and heat through the system Remark The circulator pump should run for 10 minutes during the first installation 3 Open isolation valves primary The isolation valves should then be opened and...

Страница 21: ...he handle on the thermostatic controller to select a lower number RAVK controller 35 75 C 07 see diagram Activating the thermoactuators The thermoactuators are supplied with a first open function whic...

Страница 22: ...smooths out the fluctuations in pressure arriving from the heat network The operating pressure in the heat interface unit is thus held steady AVPL can be set within the region of 5 kPa to 25 kPa 0 05...

Страница 23: ...pressure 2 factory setting Proportional pressure 3 Max Constant pressure 1 Constant pressure 2 Constant pressure 3 Max Constant curve 1 Constant curve 2 Constant curve 3 Max Function PP Red CP Green...

Страница 24: ...am IMIT Thermostat The IMIT thermostat is used to limit the underfloor heating flow temperature The IMIT thermostat is preset to 60 C and will shut off the pump and the primary on off valve when the f...

Страница 25: ...irectly on the controller The set includes circulation pipe single check valve and fitting When mounting the hot water circulation directly on the controller the hot water circulation temperature will...

Страница 26: ...sulated Isolation valve Expansion tank Double check valve WRAS Heat Exchanger The heat exchanger is produced in acid resistant stainless steel 38 see diagram 01 see diagram 2B see diagram Fill drain v...

Страница 27: ...rs including meter readings Temperatures Check of all temperatures such as DH supply temperature and DHW temperature Connections Checking all connections for leaks Safety valves The operation of the s...

Страница 28: ...normal That there is sufficient differential pressure Measures AFTER troubleshooting Once the troubleshooting has been completed undertake the following measures Tighten all union connections Wipe off...

Страница 29: ...lace the valve if defective Incorrectly set differential pressure regulator Set the differential pressure regulator to the correct value according to the section Differential pressure regulator Defect...

Страница 30: ...has been removed from the socket The unit has cooled down Gloves It is recommended that suitable work gloves are used in connection with handling and lifting of the heat interface unit Disposal This...

Страница 31: ...Danfoss 2021 06 31 LGB40450 Termix VVX I R FI 7 Series DS fully insulated Declaration of conformity...

Страница 32: ...31 21 Clip on actuator removed 69 21 Wiring completed 15 16 Mains connected Room controller connected and working Pre payment unit connected and working Pump setting completed 10 23 Correct pressure o...

Отзывы: